Nordyne M3RL Series Ventilation, START-UP and Adjustments, Start-Up Procedure

Page 26

The thermostat must not be installed on an outside wall or any other location where its operation may be adversely affected. Adverse affects include radiant loading from fireplaces, sunlight, or lighting fixtures, and convective loading from warm air registers or electrical appliances.

To check the heat anticipator setting either:

1.Add the current draw of the system com- ponents; or

2.Measure the current flow on the thermostat R-W circuit after the circulating blower motor has started.

Set the heat anticipator according to the ther- mostat manufacturer's instructions for heat anticipator settings.

VENTILATION

Ventilation must be provided for homes built to HUD Manufactured Homes Safety and Con- struction Standards. This ventilation can be sup- plied by the VentilAire III or VentilAire IV acces- sories. (See Table 12). Alternate means to pro- vide the ventilation air must meet the require- ments of all applicable local and federal codes.

For installation of the VentilAire III or IV, follow the instructions provided with the VentilAire kit.

START-UP AND ADJUSTMENTS

General

Prior to start-up, verify that:

1.The line voltage power leads are securely connected, that the polarity of the con- nections is correct, and that the furnace is properly grounded.

2.The thermostat wires (R, W, Y, and G) are securely connected to the correct leads on the terminal strip of the circuit board.

3.The natural gas line service pressure must not exceed 10.0 in. water column (0.36 psig), and must not be less than 4.5 in. water column (0.16 psig). For LP gas the line service pressure must not exceed 14 in. water column (0.51 psig), and must not be less than 11.0 in. W.C. (0.40 psig).

26

 

 

 

 

 

A/C Condensing Unit

 

 

 

 

 

 

 

 

 

Condensing Unit

 

 

 

 

 

 

 

 

 

 

 

Control Box

 

 

 

 

 

 

 

 

 

 

COM

 

 

Blower Off

60 90

120 180

 

 

R

 

 

3 Amp

 

Timing

 

R

 

 

 

 

 

 

Connect

C

 

24 V

 

Fuse

 

 

 

TWIN

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

R & W

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flame Signal Light

 

 

Heating

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

(Yellow)

 

 

Only

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Room

W

 

 

 

 

 

Status Light

 

 

 

 

 

 

 

 

 

 

9

6

3

 

 

 

 

 

(Red)

 

 

Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

5

2

 

 

 

 

 

 

 

 

 

 

 

7

4

1

 

 

 

 

 

 

 

 

 

NOTE: The "Y"

 

 

 

 

 

 

 

 

 

 

 

 

terminal on the

 

 

 

 

 

 

 

 

 

 

 

 

UTEC control board

 

 

 

 

 

 

 

 

 

 

 

 

must be connected

EAC

 

 

 

 

 

 

 

 

 

 

 

to the thermostat

 

 

 

 

 

 

 

 

 

 

 

for proper cooling

 

Neutrals

 

 

 

 

 

 

 

mode operation.

HUM

 

 

 

 

 

 

 

 

FIELD WIRING

 

 

Unused Motor Leads

 

 

 

 

 

6

3

HUM

 

COOL

HEAT

XFMR EAC

 

 

 

Low Voltage

 

 

M3 M2 M1

 

L1

 

 

 

5

2

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

1

 

 

 

 

 

 

 

 

Figure 28. Low Voltage Field,

Four-wire Heating/Cooling Applications

4.The roll-out and vent safety manual reset switches are closed. If necessary, press the red button to reset a switch. See Figure 26 for location. DO NOT install a jumper wire across a switch to defeat its function. If a switch reopens on start-up, DO NOT reset the switch without identify- ing and correcting the fault condition which caused the switch to trip.

5.The blower door is in place, closing the door switch in the line voltage circuit.

6.The gas line has been purged and all connections are leak tight.

Start-Up Procedure

1.Set the thermostat to the lowest setting.

2.Close the disconnect(s) to provide line voltage to the furnace.

3.Follow the procedures given on the oper- ating instructions label attached to the furnace.

4.Set the thermostat above room tempera- ture and verify the sequence of operation. (See the SEQUENCE OF OPERATION.)

Image 26
Contents Installation Instructions Page Table of Contents L 060 a a WGeneral Shipping WeightFurnace Specifications/Airflow Data Top ViewOwner Information General DescriptionInstallation Standards Manufacturer WARRANTY, OWNER’S ResponsibilitiesMinimum Clearances LocationCirculating AIR Supply Duct Connectors Return AIR ProvisionsCloset or Alcove Ducted Return AIRAIR Distribution Systems Duct Connector SelectionDuct Installation CUT Duct Opening Finger Tabbed only Installing Platinum Series 14 Round Duct ConnectorInstalling Screw Down Duct CON- Nector Screw Down Platinum SeriesInstalling Finger Tabbed Duct CON- Nectors Alternate Attachment MethodsGeneral Install FurnaceVenting and Combustion AIR Requirements Venting Requirements Furnace Must not be Common Vented with Other AppliancesVent Table Vent Termination Clearances for Direct Vent FurnacesVent Pipe Installation Vent Pipe MaterialDownflow Furnace Horizontal VentingHorizontal Venting Alternate Horizontal Vent Installation Drainage of Condensate from FurnaceFurnace with Condensate Drain Trap Assembly GAS Supply and PipingHigh Altitude Derate ConversionLeak Check To Turn Off Fuel Supply to the ApplianceTo Convert the Unit to the Alternate Gas To Remove the Burner AssemblyTo Remove the Burner Orifices Approximate Orifice Size for Natural and LP GasesLighting and Adjustment of the Appliance Convertible Pressure Regulator CapType of Fuel Manifold Pressure Electrical WiringLine Voltage Wiring Completing the ConversionLow Voltage Wiring Electrical DataVentilation START-UP and AdjustmentsStart-Up Procedure Verifying Firing Rate Shut Down ProcedureSequence of Operation Gas Flow Rate Verifying Operation of the Supply Air Limit SwitchDescription of Components Verifying Burner OperationCombustion Air and Vent System MaintenanceAccessory Kits Air FilterLubrication Condensate Drain AssemblySystem Operation Information Blower CompartmentCooling Mode Furnace Fails to OperateM3 Downflow Furnace Downflow Furnace Wiring Diagram Page INSTALLATION/PERFORMANCE Check List Fuel Type¢7082197¤

M3RL Series specifications

The Nordyne M3RL Series is a cutting-edge line of residential heating and cooling systems designed to enhance home comfort while emphasizing energy efficiency and reliability. Engineered with the latest technologies, the M3RL Series stands out as a premier choice for homeowners seeking optimal climate control, advanced features, and quiet operation.

One of the standout characteristics of the Nordyne M3RL Series is its high-efficiency performance. With Seasonal Energy Efficiency Ratios (SEER) that surpass industry standards, these systems deliver exceptional cooling power while using less energy. This efficiency not only translates to lower utility bills but also reduces the environmental footprint, making the M3RL Series an eco-friendly option.

Incorporating advanced inverter technology, the M3RL Series units operate at varying speeds, allowing them to adjust cooling and heating output to match the current demand. This feature ensures consistent temperature control while minimizing energy consumption. The systems are also equipped with a variable-speed compressor, which works in harmony with the inverter technology to provide seamless operation and quiet performance.

The M3RL Series showcases durability through its robust construction. The outdoor units feature a powder-coated finish to withstand the elements, while the indoor components are designed with high-quality materials to ensure longevity. The environmentally friendly refrigerant used in these systems further emphasizes Nordyne's commitment to sustainability.

Another notable aspect is the advanced control options available with the M3RL Series. Homeowners can choose from various thermostat solutions, including smart thermostats that offer remote control capabilities and programming features. This flexibility allows users to optimize their heating and cooling schedules, enhancing both comfort and efficiency.

In terms of installation, the M3RL Series is designed with versatility in mind. The compact and lightweight design of the units ensures ease of placement in various home layouts, while the comprehensive installation manuals and support from Nordyne make the process straightforward for HVAC professionals.

The Nordyne M3RL Series is truly a hallmark of modern home climate control, embodying efficiency, durability, and advanced technology. With its combination of high-performance features, user-friendly controls, and a commitment to sustainability, it provides an ideal solution for homeowners looking to enhance comfort while reducing energy costs. The M3RL Series represents a significant step forward in the evolution of residential heating and cooling systems.