Nordyne M3RL Series installation instructions Cooling Mode, Furnace Fails to Operate

Page 31

Initial Power up: After 30 seconds of igniter warm-up the gas valve (24 VAC) will then open. The igniter circuit will stay ener- gized for 3 seconds after the gas valve opens.

After Initial Power up: The control has a programmed adaptive ignition feature which varies the warm-up period as fol- lows: If ignition is successful the warm-up is reduced by 3-seconds on each subsequent call for heat until ignition failure occurs. Upon ignition failure, the warm-up is in- creased by 3-seconds on the next try. If successful, the timing remains fixed at this level. In general, whenever ignition failure occurs the warm-up interval is increased by 3-seconds on the next try. And if success- ful, it remains there. Minimum and maxi- mum warm-up time limits are set at 6 and 54-seconds, respectively.

7.The furnace control must prove flame via the flame sensor 5 seconds after the gas valve opens. If flame is sensed, all burn- ers are on and the ignitor cools off. If no flame is sensed, the gas valve closes immediately and the inducer continues to run. A second trial for ignition (step 6) begins if no flame is sensed. On the fifth try for ignition, the furnace control is locked out and the red LED will blink 4 times repetitively. The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out. Oth- erwise, the furnace will attempt another ignition sequence in 1 hour.

8.The furnace control energizes the cir- culating air blower on the heating speed 30 seconds after the gas valve circuit is energized .

9.When the thermostat has been satisfied,

gas valve is de-energized.

10.The inducer is de-energized after a 30- second postpurge.

11.The furnace control keeps the circulating air blower energized for 120 seconds (factory set) or 60, 90, or 180 seconds (field adjustable). (See Figure 27.)

12.Abnormal conditions: If a limit opens during operation, the inducer and circulating air blower continue to operate. The gas valve is de-energized immediately. The blowers continue to operate until the limit closes. When the limit closes the inducer blower is de-energized immediately. The circulating air blower continues to operate for the speci- fied delay (factory set at 120 seconds).

Cooling Mode:

1.On a call for cooling the thermostat closes, applying 24 VAC to the G and Y terminals on the furnace control. This closes the compressor contactor.

2.The furnace control energizes the circu- lating blower (115 VAC) on the cooling speed.

3.When the thermostat is satisfied, the G and Y terminals on the control board are de-energized opening the compressor contactor.

4.The circulating air blower is de-energized after a 90-second delay.

Fan Mode:

1.On a call for fan operation, the thermostat applies 24 VAC to the G terminal on the furnace control board.

2.The circulating air blower is energized immediately on the heating speed.

3.If the furnace is operated in the continu- ous ON position at the thermostat and is then switched to AUTO, the circulating blower will operate for a specified delay (factory set at 120 seconds).

Furnace Fails to Operate

If the furnace does not operate check the following:

1.Is the thermostat operating properly?

2.Is the front door in place?

3.Is the furnace disconnect closed?

4.Has the circuit breaker tripped or the control board fuse burned open?

5.Is the gas turned on?

6.Are any manual reset switches open?

7.Is the filter dirty or plugged?

8.Is the flame sensor coated? (Remove and clean with emery cloth.)

9.Is the deck switch open?

If the furnace locks out after 5 attempts for ignition, it will try again every hour if a call for heat remains. If the inducer and circulating air blowers are operating, and items 1 through 8 have been checked, press the red reset but- ton on the vent safety switch. (See Figure 29.) If the furnace operates after depressing the reset button, contact a qualified service tech- nician to identify and repair the problem.

If furnace still fails to operate, depress the red reset buttons on the flame roll-out switch. If the furnace operates after depressing the reset button, contact a qualified service tech- nician to identify and repair the problem.

31

Image 31
Contents Installation Instructions Page L 060 a a W Table of ContentsTop View Shipping WeightFurnace Specifications/Airflow Data GeneralGeneral Description Owner InformationManufacturer WARRANTY, OWNER’S Responsibilities Installation StandardsCirculating AIR Supply LocationMinimum Clearances Return AIR Provisions Duct ConnectorsDucted Return AIR Closet or AlcoveDuct Installation Duct Connector SelectionAIR Distribution Systems Screw Down Platinum Series Installing Platinum Series 14 Round Duct ConnectorInstalling Screw Down Duct CON- Nector CUT Duct Opening Finger Tabbed onlyAlternate Attachment Methods Installing Finger Tabbed Duct CON- NectorsVenting and Combustion AIR Requirements Install FurnaceGeneral Furnace Must not be Common Vented with Other Appliances Venting RequirementsVent Termination Clearances for Direct Vent Furnaces Vent TableVent Pipe Material Vent Pipe InstallationHorizontal Venting Downflow FurnaceHorizontal Venting Drainage of Condensate from Furnace Alternate Horizontal Vent InstallationGAS Supply and Piping Furnace with Condensate Drain Trap AssemblyTo Turn Off Fuel Supply to the Appliance ConversionLeak Check High Altitude DerateApproximate Orifice Size for Natural and LP Gases To Remove the Burner AssemblyTo Remove the Burner Orifices To Convert the Unit to the Alternate GasConvertible Pressure Regulator Cap Lighting and Adjustment of the ApplianceCompleting the Conversion Electrical WiringLine Voltage Wiring Type of Fuel Manifold PressureElectrical Data Low Voltage WiringStart-Up Procedure START-UP and AdjustmentsVentilation Sequence of Operation Shut Down ProcedureVerifying Firing Rate Verifying Burner Operation Verifying Operation of the Supply Air Limit SwitchDescription of Components Gas Flow RateAir Filter MaintenanceAccessory Kits Combustion Air and Vent SystemBlower Compartment Condensate Drain AssemblySystem Operation Information LubricationFurnace Fails to Operate Cooling ModeM3 Downflow Furnace Downflow Furnace Wiring Diagram Page Fuel Type INSTALLATION/PERFORMANCE Check List¢7082197¤

M3RL Series specifications

The Nordyne M3RL Series is a cutting-edge line of residential heating and cooling systems designed to enhance home comfort while emphasizing energy efficiency and reliability. Engineered with the latest technologies, the M3RL Series stands out as a premier choice for homeowners seeking optimal climate control, advanced features, and quiet operation.

One of the standout characteristics of the Nordyne M3RL Series is its high-efficiency performance. With Seasonal Energy Efficiency Ratios (SEER) that surpass industry standards, these systems deliver exceptional cooling power while using less energy. This efficiency not only translates to lower utility bills but also reduces the environmental footprint, making the M3RL Series an eco-friendly option.

Incorporating advanced inverter technology, the M3RL Series units operate at varying speeds, allowing them to adjust cooling and heating output to match the current demand. This feature ensures consistent temperature control while minimizing energy consumption. The systems are also equipped with a variable-speed compressor, which works in harmony with the inverter technology to provide seamless operation and quiet performance.

The M3RL Series showcases durability through its robust construction. The outdoor units feature a powder-coated finish to withstand the elements, while the indoor components are designed with high-quality materials to ensure longevity. The environmentally friendly refrigerant used in these systems further emphasizes Nordyne's commitment to sustainability.

Another notable aspect is the advanced control options available with the M3RL Series. Homeowners can choose from various thermostat solutions, including smart thermostats that offer remote control capabilities and programming features. This flexibility allows users to optimize their heating and cooling schedules, enhancing both comfort and efficiency.

In terms of installation, the M3RL Series is designed with versatility in mind. The compact and lightweight design of the units ensures ease of placement in various home layouts, while the comprehensive installation manuals and support from Nordyne make the process straightforward for HVAC professionals.

The Nordyne M3RL Series is truly a hallmark of modern home climate control, embodying efficiency, durability, and advanced technology. With its combination of high-performance features, user-friendly controls, and a commitment to sustainability, it provides an ideal solution for homeowners looking to enhance comfort while reducing energy costs. The M3RL Series represents a significant step forward in the evolution of residential heating and cooling systems.