Nordyne M3RL Series Venting and Combustion AIR Requirements, General, Install Furnace

Page 13

SLIDE FURNACE

MTG. PLATE TABSALL THE WAY BACK

ONTO MTG. PLATE

SECURE FURNACE

WITH 2 FASTENERS AT FRONT

CORNER HOLES

Knockout Over Holes

SUPPLY AIR DUCT

Figure 13. “A”, “B”, & Platinum Cabinet Furnaces

NOTE: Additional fasteners may be used at rear, sides or through door frame, as desired, to secure furnace to closet or alcove framing.

VENTING AND COMBUSTION AIR REQUIREMENTS

!CAUTION:

Snow must not be allowed to restrict or block the combustion air intake or vent pipes.

General

FUEL

LINE HOLES

MTG. PLATE TABS

SECURE FURNACE WITH 2 FASTENERS

AT FRONT CORNER HOLES

SUPPLY AIR DUCT

SLIDE FURNACE

ALL THE WAY BACK ONTO MTG. PLATE

NORDYNE condensing furnaces must be installed with outdoor combustion air piped directly to the furnace. Codes refer to this type of installation as direct vent, or two pipe installation.

Provisions must be made for adequate supply of air for combustion and ventilation. For United States installations, the adequacy of air provisions can be determined by consulting

Figure 14. “A” Cabinet Furnace on 911969 Coil Cabinet (Non-Platinum Series)

3.At the front-to-back of duct run (Area “A”), bend the duct tabs and secure them directly to the duct.

4.At Area “B”, bend the duct tabs up and back over, around the duct connector, (See Step 3).

5.Fold/form the duct flap against the side of the duct connector and attach as shown, (See Step 4). Use three (3) staples (minimum) on each duct flap OR, if a 2X block/joist is not provided, use two (2) sheet metal screws (minimum) on each duct flap. An alternate attachment method is acceptable, as long as the plenum is securely attached.

6.Tape the duct flap edges with an approved tape for a leak-free joint.

INSTALL FURNACE

a. Remove furnace outer door(s) and bottom fuel line knockout.

b. Place furnace onto duct connector and cen- ter with floor opening.

c.Slide onto mounting plate. (Bottom rear slots on furnace should engage with mounting plate tabs.)

d.Secure front with one (1) fastener at each corner (See Figure 13 or 14).

the current version of the National Fuel Gas Code (ANSI Z223.1/NPFA-54). For Canadian installations, requirements are specified in the National Standard of Canada (CAN/CGA B149.1 & .2). Consult local codes for special requirements.

NOTE: If the furnace is operated without adequate air for combustion and ventilation, it may not perform properly. Furnace components may be strained by high temperature and could fail prematurely.

!WARNING:

The combustion air piping must not be blocked or restricted in any manner.

!WARNING:

Furnace installation using methods other than those described in the following sections must comply with the National Fuel Gas Code and all applicable local codes to provide sufficient combustion air for the furnace.

13

Image 13
Contents Installation Instructions Page L 060 a a W Table of ContentsFurnace Specifications/Airflow Data Shipping WeightGeneral Top ViewGeneral Description Owner InformationManufacturer WARRANTY, OWNER’S Responsibilities Installation StandardsCirculating AIR Supply LocationMinimum Clearances Return AIR Provisions Duct ConnectorsDucted Return AIR Closet or AlcoveDuct Installation Duct Connector SelectionAIR Distribution Systems Installing Screw Down Duct CON- Nector Installing Platinum Series 14 Round Duct ConnectorCUT Duct Opening Finger Tabbed only Screw Down Platinum SeriesAlternate Attachment Methods Installing Finger Tabbed Duct CON- NectorsVenting and Combustion AIR Requirements Install FurnaceGeneral Furnace Must not be Common Vented with Other Appliances Venting RequirementsVent Termination Clearances for Direct Vent Furnaces Vent TableVent Pipe Material Vent Pipe InstallationHorizontal Venting Downflow FurnaceHorizontal Venting Drainage of Condensate from Furnace Alternate Horizontal Vent InstallationGAS Supply and Piping Furnace with Condensate Drain Trap AssemblyLeak Check ConversionHigh Altitude Derate To Turn Off Fuel Supply to the ApplianceTo Remove the Burner Orifices To Remove the Burner AssemblyTo Convert the Unit to the Alternate Gas Approximate Orifice Size for Natural and LP GasesConvertible Pressure Regulator Cap Lighting and Adjustment of the ApplianceLine Voltage Wiring Electrical WiringType of Fuel Manifold Pressure Completing the ConversionElectrical Data Low Voltage WiringStart-Up Procedure START-UP and AdjustmentsVentilation Sequence of Operation Shut Down ProcedureVerifying Firing Rate Description of Components Verifying Operation of the Supply Air Limit SwitchGas Flow Rate Verifying Burner OperationAccessory Kits MaintenanceCombustion Air and Vent System Air FilterSystem Operation Information Condensate Drain AssemblyLubrication Blower CompartmentFurnace Fails to Operate Cooling ModeM3 Downflow Furnace Downflow Furnace Wiring Diagram Page Fuel Type INSTALLATION/PERFORMANCE Check List¢7082197¤

M3RL Series specifications

The Nordyne M3RL Series is a cutting-edge line of residential heating and cooling systems designed to enhance home comfort while emphasizing energy efficiency and reliability. Engineered with the latest technologies, the M3RL Series stands out as a premier choice for homeowners seeking optimal climate control, advanced features, and quiet operation.

One of the standout characteristics of the Nordyne M3RL Series is its high-efficiency performance. With Seasonal Energy Efficiency Ratios (SEER) that surpass industry standards, these systems deliver exceptional cooling power while using less energy. This efficiency not only translates to lower utility bills but also reduces the environmental footprint, making the M3RL Series an eco-friendly option.

Incorporating advanced inverter technology, the M3RL Series units operate at varying speeds, allowing them to adjust cooling and heating output to match the current demand. This feature ensures consistent temperature control while minimizing energy consumption. The systems are also equipped with a variable-speed compressor, which works in harmony with the inverter technology to provide seamless operation and quiet performance.

The M3RL Series showcases durability through its robust construction. The outdoor units feature a powder-coated finish to withstand the elements, while the indoor components are designed with high-quality materials to ensure longevity. The environmentally friendly refrigerant used in these systems further emphasizes Nordyne's commitment to sustainability.

Another notable aspect is the advanced control options available with the M3RL Series. Homeowners can choose from various thermostat solutions, including smart thermostats that offer remote control capabilities and programming features. This flexibility allows users to optimize their heating and cooling schedules, enhancing both comfort and efficiency.

In terms of installation, the M3RL Series is designed with versatility in mind. The compact and lightweight design of the units ensures ease of placement in various home layouts, while the comprehensive installation manuals and support from Nordyne make the process straightforward for HVAC professionals.

The Nordyne M3RL Series is truly a hallmark of modern home climate control, embodying efficiency, durability, and advanced technology. With its combination of high-performance features, user-friendly controls, and a commitment to sustainability, it provides an ideal solution for homeowners looking to enhance comfort while reducing energy costs. The M3RL Series represents a significant step forward in the evolution of residential heating and cooling systems.