Nordyne M3RL Series installation instructions Location, Circulating AIR Supply, Minimum Clearances

Page 7

CE générateur d'air chaud doit être installé conformément aux instructions du fabricant et aux codes locaux. En l'absence de code local, respecter la norme ANSI Z223.,1, institulé Na- tional Fuel Gas Code ou les codes d'installation CAN/GCA-B149.

The National Fuel Gas Code is available by writing:

American National Standards Institute, Inc.

1430 Broadway

New York, NY 10018

NFPA publications are available by writing:

National Fire Protection Association

Batterymarch Park

Quincy, ME 02269

LOCATION

The furnace must be installed on a level sur- face, and as close to the center of the air distribution system as possible. See Figure 1 for overall dimensions to determine the re- quired clearances in hallways, doorways, stairs, etc. to allow the furnace to be moved to the installation point. The furnace must be in- stalled so that all electrical components are protected from water.

Minimum clearances to combustible materials are listed in Table 4. Access for positioning and servicing must be considered when locating the unit.

This furnace is certified for use on wood flooring. The furnace must be installed on a solid surface and must be level front-to-back and side-to-side. This furnace must not be installed directly on carpeting, tile, or any com-

 

CLOSET

ALCOVE

ALL MODELS

Inches

Inches

Front

1*

1*

Back

0

0

Sides

0

0

Vent

0

0

Top

6

6

Duct (Plenum)

 

 

w/ Coil Box

0

0

w/o Coil Box

1/4

1/4

(within 3 feet)

 

 

*Note: For 1” clearance, use a fully louvered door with at least 400 square inches of free airflow area.

Table 4. Minimum Clearances

bustible material other than wood flooring. The furnace may be installed on combustible floor- ing when installed on a Nordyne duct connec- tor (see Table 5).

The ductwork within 3 feet of the furnaces without the A/C coil box must be installed such that surfaces are at least 1/4" from combustible materials.

When installed in a residential garage, the fur- nace must be positioned so the burners and the source of the ignition are located no less than 18 inches above the floor and protected from physical damage by vehicles.

CIRCULATING AIR SUPPLY

!WARNING:

Products of combustion must not be allowed to enter the return air openings of the furnace or the circulating air supply. Failure to prevent products of combustion from being circulated into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.

The floor or platform on which the furnace is mounted must provide sound physical support of the furnace with no gaps, cracks, or sagging between the furnace and the floor or platform.

The circulating air ductwork must not be connected to any other heat producing device such as a fireplace insert, stove, etc.

GENERAL

Plenums and air ducts must be installed in accordance with the Standard for the Installa- tion of Air Conditioning and Ventilating Systems (NFPA No. 90A) or the Standard for the Instal- lation of Warm Air Heating and Air Conditioning Systems (NFPA No. 90B).

7

Image 7
Contents Installation Instructions Page L 060 a a W Table of Contents Top View Shipping Weight Furnace Specifications/Airflow Data GeneralGeneral Description Owner InformationManufacturer WARRANTY, OWNER’S Responsibilities Installation StandardsCirculating AIR Supply LocationMinimum Clearances Return AIR Provisions Duct ConnectorsDucted Return AIR Closet or AlcoveDuct Installation Duct Connector SelectionAIR Distribution Systems Screw Down Platinum Series Installing Platinum Series 14 Round Duct ConnectorInstalling Screw Down Duct CON- Nector CUT Duct Opening Finger Tabbed onlyAlternate Attachment Methods Installing Finger Tabbed Duct CON- NectorsVenting and Combustion AIR Requirements Install FurnaceGeneral Furnace Must not be Common Vented with Other Appliances Venting RequirementsVent Termination Clearances for Direct Vent Furnaces Vent TableVent Pipe Material Vent Pipe InstallationHorizontal Venting Downflow FurnaceHorizontal Venting Drainage of Condensate from Furnace Alternate Horizontal Vent InstallationGAS Supply and Piping Furnace with Condensate Drain Trap AssemblyTo Turn Off Fuel Supply to the Appliance ConversionLeak Check High Altitude DerateApproximate Orifice Size for Natural and LP Gases To Remove the Burner AssemblyTo Remove the Burner Orifices To Convert the Unit to the Alternate GasConvertible Pressure Regulator Cap Lighting and Adjustment of the ApplianceCompleting the Conversion Electrical WiringLine Voltage Wiring Type of Fuel Manifold PressureElectrical Data Low Voltage WiringStart-Up Procedure START-UP and AdjustmentsVentilation Sequence of Operation Shut Down ProcedureVerifying Firing Rate Verifying Burner Operation Verifying Operation of the Supply Air Limit SwitchDescription of Components Gas Flow RateAir Filter MaintenanceAccessory Kits Combustion Air and Vent SystemBlower Compartment Condensate Drain AssemblySystem Operation Information LubricationFurnace Fails to Operate Cooling ModeM3 Downflow Furnace Downflow Furnace Wiring Diagram Page Fuel Type INSTALLATION/PERFORMANCE Check List¢7082197¤