INSTALLATION

MATERIALS REQUIRED

CLEARANCES

No electrical power supply is required for the gas control to operate. A 120 Volt AC power cord is hooked up to the fan switch and blower. Plug 3 wire cord into a suitable receptacle. Do not cut the ground terminal off under any circumstances.

When connected with 120 volts, the appliance must be electrically grounded in accordance with local codes, with a current version of CSA C22.1 (in Canada) or in the absence of local codes, with the National Electrical Code ANSI/ NFPA 70-1987.

Note: This unit is equipped with a heat sen- sor thermodiscwhichwillpreventthe blower from operating until the unit reaches the correct temperature.

INSTALLATION

CHECKLIST

The Regency Gas Insert is installed as listed below.

1)

Unit Location - check Clearances to Com-

 

bustibles.

2)

Make the gas connections and electrical

 

connection for fan and vent spill switch.

3)

Install the fl ue or liner to the sliding draft

 

hood.

4)

Install Venting. Slide the unit into the fi re-

 

place and level. Attach draft hood to the

 

insert.

5)

Test gas pressure. Check aeration.

6)

Test for fl ue spillage.

7)

Assemble and install the faceplate and

 

trim.

8)

Install the log set.

Minimum Fireplace Clearances

The minimum fi replace clearances for the Regency gas fi replace insert are shown in the following diagrams:

Clearances to Combustibles

From Unit

 

Sides

A

7.5" / 190 mm

Ceiling

B

35" / 890 mm

Mantel

C(My)

11 / 280 mm

From Surround

 

Sides

D

2" / 50 mm

Ceiling

E

25.5" / 650 mm

Mantel

F

3" / 75 mm

Min. Alcove Width

J

48" / 1120 mm

Mantel Depth

G(Mx)

7.5" / 190 mm

Facing (Mantel Leg)

 

 

Side*

K

1" / 25 mm

Top

L

1" / 25 mm

*Max. width of 1" at 1" from surround, calculate

B

 

 

E

 

 

G

 

F

 

C

 

I

 

 

A

 

 

D

H

J

 

9)

Install Doors.

10)

Install Remote Control & Wall Thermostat

11)

Explain controls to the homeowner.

Final check: Before leaving this unit with the customer, the installer must ensure that the ap- pliance is fi ring correctly. This includes:

a)Clocking the appliance to ensure the correct fi ring rate.

b)Adjusting the primary air, if required, to ensure that the fl ame does not carbon.

c)Ensuring that the appliance is venting correctly.

depth at 45o as shown in the diagram.

Top View

Regency U41-3 ULTIMATE Gas Fireplace Insert

7

Image 7
Contents 908-727c 07/17/06 U41 Gas InsertTo the NEW Owner Regency GAS Fireplace InsertTable of Contents Do not Remove this Label Safety LabelMA Code CO Detector RequirementsInstallation Clearances Installation ChecklistCombustible Mantel Clearances High ElevationNon-combustible Hearth Extension Draft Hood Connection Combustion Ventilation AIR GAS ConnectionVenting Aeration System GAS Pressure TestTest for Flue Spillage Faceplate panel Faceplate and Trim InstallationDoor Installation Packaged Separately LOG InstallationManufacturer Final CheckWiring Diagram Operating Instructions Copy of the Lighting Plate Instructions For Your Safety Readbefore LightingMaintenance Instructions MaintenanceNormal Operating Sounds GAS Appliances GOLD-PLATED Doors LOG ReplacementLatch Adjustment Glass ReplacementReplacing fan FAN MaintenanceMain Assembly Parts ListBurner & Logs Description Faceplate & TrimConditions WarrantyInstaller Please complete the following information