Desa (V)T32EP-A SERIES, (V)T32EN-A SERIES Installation for vertical termination

Page 14

Venting Installation

instructions

Continued

installation for vertical termination

Note: Vertical restrictor must be installed in all vertical installations.

1.Determine the route your vertical venting will take. If ceiling joists, roof rafters or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cut- ting load bearing members. Note: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations.

2.Set the fireplace in desired location. Drop a plumb line down from the ceiling to the posi- tion of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Roof

Flashing

Wall Strap

45° Elbow

Ceiling

Firestop

Figure 19 - Offset with Wall Strap and 45°

Elbows

Flat Ceiling Installation

1. Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4"x10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 8 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

2. Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Figure 8, page 9).

3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4"x10 3/4" hole must be measured on the horizontal; actual length may be larger depend- ing on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 9.

4. Connect a section of pipe and extend up through the hole.

Note: If an offset is needed to avoid obstruc- tions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Fig- ure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material over- laps the top edge of the flashing as shown in Figure 19. There must be a 1" clearance from the vent pipe to combustible materials.

If area above is a

If area above is not a

room or insulated

room, install firestop

area, install firestop

below framed hole.

above framed hole.

 

Figure 20 - Installing Firestop

14

www.desatech.com

116647-01B

Image 14
Contents What to do if YOU Smell GAS Table of Contents Safety InformationSafety Information Local Codes Product FeaturesProduct Identification Clearances Pre-Installation PreparationLocation and space requirements Flush with a wallFraming and finishing Location of Termination Cap Termination CAP AIR Supply Inlet GAS MeterVenting Installation Instructions Installation PrecautionsCenter Installation PlanningMale Slots Female Locking Lugs HoleVent Cap Wood Screw Noncombustible ExteriorHorizontal H Venting InstallationSquare Termination 53 3/4 min Wall Firestop Elbow43 3/4 min None 65 3/4 minVertical V Horizontal H Venting with Two 90 ElbowsMin Max 12 max 18 max 20 max Elbow Min Max 12 max 18 max Elbow 20 maxRoof Flashing Wall Strap Elbow Ceiling Firestop Installation for vertical terminationFlat Ceiling Installation If area above is aMin Max 12 max 18 max 20 max Min Max 20 max ElbowVenting with One 90 Elbow Vertical V Horizontal H Vertical Venting High Altitude InstallationParts list for venting kits and components = 40 max ElbowModel BK Installation Fireplace InstallationInstalling optional blower accessory Check GAS TypeRight outside Wiring Diagram Decal 12 in Front BlowerModel BKT Installation Blower Wiring Diagram Blower Model BKTInstalling Gas Piping to Fireplace Location Installation Items NeededRed Surface Connecting Fireplace to GAS SupplyChecking GAS Connections Test Pressures Equal To or Less Than Psig 3.5 kPa Pressure Testing Fireplace Gas ConnectionsRemoving/Replacing Glass Door Removing Louver PanelsRemoving Glass Door Installing Optional Brick liner Model BL32DCleaning Glass Door Installing logs, lava rock and glowing embers Left Side Brick PanelWall Switch Installation Optional Remote control Installation model WRCOperating Fireplace Wiring DiagramFor Your Safety Read Before Lighting Lighting InstructionsOptional Remote Operation Operating optional blower accessoryTo Turn OFF GAS To Appliance Inspecting Burners Cleaning MaintenancePilot Assembly Burner Flame PatternVenting system Pilot and burnersLogs Troubleshooting Observed Problem Possible Cause RemedyGas leak. See Warning Checking Gas ConnectionsTechnical Service Replacement PartsService Hints SpecificationsAccessories Remote Control KIT WRCIllustrated Parts Breakdown 22-1 1141814123 21171 24353 24460 22-2109 Electronic Valve Propane/LP 116647-01B 116647-01B Limited Warranty DIRECT-VENT Fireplace Warranty InformationKeep this Warranty