Desa BDV34N(A) installation manual Connecting Fireplace to GAS Supply, Checking GAS Connections

Page 19

OWNER’S MANUAL

FIREPLACE INSTALLATION

Continued

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gen- tly pulling forward.

2.Route flexible gas line (provided by installer) from manual shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas sup- ply to control valve (see Figure 36).

4.Check all gas connections for leaks. See Checking Gas Connections.

To Gas Supply

Manual Shutoff Valve

(Natural)

 

To External Regulator (Propane)

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply commercial leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

Control Valve

3.Pressurize supply piping system by ei- ther opening propane supply tank valve for propane gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, or using compressed air.

4.Check all joints of gas supply piping system. Apply commercial leak test solution to all gas joints. Bubbles form- ing show a leak. Correct all leaks at once.

5.Reconnect fireplace and manual shutoff valve to gas supply. Check reconnected fittings for leaks.

Flexible Gas Line from

Manual Shutoff Valve

Provided by Installer

Figure 36 - Attaching Flexible Gas Lines To The Control Valve

Continued

105453

19

Image 19
Contents For Your Safety What to do if YOU Smell GAS For Your SafetyBDV34NA and BDV34PA DIRECT-VENT Fireplace NATURAL/PROPANE Safety InformationGlossary Terms Product FeaturesProduct Identification Local CodesFraming and Finishing PRE-INSTALLATION PreparationClearances Location and Space RequirementsLocation of Vent Termination General VentingGeneral Venting Installing Vent System in a Chase Venting InstallationInstallation Precautions Installation PlanningSnorkel Termination Installation for Horizontal TerminationVent Pipe Connections Horizontal Venting Horizontal Termination ConfigurationsVenting with Two 90 Elbows Flat Ceiling Installation Installation for Vertical TerminationCathedral Ceiling Installation Venting with One 90 Elbow Vertical Termination ConfigurationsVertical Venting Vertical Rigid Venting Configuration Using Two 90 ElbowsVanguard Flexible Venting High Altitude InstallationParts Lists for Venting Kits and Components Vanguard Rigid VentingCheck GAS Type Fireplace InstallationInstalling Optional Blower Accessory Installing GA3700/DA3610T BlowersSide View As a freestanding unit with an acInstallation Items Needed Installing GAS Piping to Fireplace LocationTest Pressures In Excess Of 1/2 Psig 3.5 kPa Connecting Fireplace to GAS SupplyPressure Testing Gas Supply Piping System Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Installing Optional Wall Mount Switch GWMS2Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Installing 9-Volt Battery in Hand- Held Remote Control Unit Installing Remote ReceiverREMOVING/REPLACING Glass Door Installing Left Side Brick Panel Installing Optional Brick Liner D8037Fireplace Models BDV34NA and BDV34PA Installing LOGS, Lava Rock and Glowing EmbersLighting Instructions For Your Safety Read Before LightingManual Lighting Procedure Operating FireplaceOptional Remote Operation Operating Optional Blower AccessoryPilot Assembly Inspecting BurnersCleaning and Maintenance Observed Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Above Gas leak. See Warning statementParts Under Warranty Replacement Wiring Diagram PartsTechnical Service Service HintsBDV34NA BDV34PA SpecificationsAccessories Brass Louver KIT Receiver and HAND-HELD Remote Control KIT Ghrc SeriesON/OFF Wall Mount Switch GWMS2 Duplex Outlet KIT GA3555 not ShownIllustrated PARTS37 Breakdown DIRECT-VENT Fireplace BDV34NA Parts ListBDV34PA7 DIRECT-VENT Fireplace BDV34PA Warranty Information