OWNER’S MANUAL

TROUBLESHOOTING

Note: For additional help, visit DESA International’s Technical Service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean pilot. This can damage pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no spark at pilot

1.Ignitor electrode not connected to igni- tor cable

2.Ignitor cable pinched or wet

3.Piezo ignitor nut is loose

4.Broken ignitor cable

5.Bad piezo ignitor

6.Ignitor electrode broken

7.Ignitor electrode positioned wrong

1.Reconnect ignitor cable

2.Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry

3.Tighten nut holding piezo ignitor. Nut is located behind the mounting bracket.

4.Replace ignitor cable

5.Replace piezo ignitor

6.Replace pilot assembly

7.Replace pilot assembly

When ignitor button is pressed, there is spark at pilot but no ignition

1.Gas supply turned off or manual shutoff valve closed

2.Control knob not in PILOT position

3.Control knob not pressed in while in PILOT position

4.Air in gas lines when installed

5.Depleted gas supply (propane models only)

6.Pilot is clogged

7.Gas regulator setting is not correct

1.Turn on gas supply or open manual shutoff valve

2.Turn control knob to PILOT position

3.Press in control knob while in PILOT position

4.Continue holding down control knob. Repeat igniting operation until air is removed

5.Contact local propane gas company

6.Clean pilot (see Cleaning and Maintenance, page 26) or replace pilot assembly

7.Replace gas control

Pilot lights but flame goes out when control knob is released

1.Control knob not fully pressed in

2.Control knob not pressed in long enough

3.Manual shutoff valve not fully open

4.Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob- lem could be caused by one or both of the following:

A)Low gas pressure

B)Dirty or partially clogged pilot

5.Thermocouple connection loose at con- trol valve

6.Thermocouple damaged

7.Control valve damaged

1.Press in control knob fully

2.After pilot lights, keep control knob pressed in 30 seconds

3.Fully open manual shutoff valve

4.A) Contact local gas company

B)Clean pilot (see Cleaning and Maintenance, page 26) or replace pilot assembly

5.Hand tighten until snug, then tighten 1/4 turn more

6.Replace thermocouple

7.Replace control valve

www.desatech.com

Continued

105453

27

Image 27
Contents For Your Safety For Your Safety What to do if YOU Smell GASBDV34NA and BDV34PA DIRECT-VENT Fireplace NATURAL/PROPANE Safety InformationGlossary Terms Product FeaturesProduct Identification Local CodesFraming and Finishing PRE-INSTALLATION PreparationClearances Location and Space RequirementsLocation of Vent Termination General VentingGeneral Venting Installing Vent System in a Chase Venting InstallationInstallation Precautions Installation PlanningSnorkel Termination Installation for Horizontal TerminationVent Pipe Connections Horizontal Venting Horizontal Termination ConfigurationsVenting with Two 90 Elbows Installation for Vertical Termination Flat Ceiling InstallationCathedral Ceiling Installation Venting with One 90 Elbow Vertical Termination ConfigurationsVertical Venting Vertical Rigid Venting Configuration Using Two 90 ElbowsVanguard Flexible Venting High Altitude InstallationParts Lists for Venting Kits and Components Vanguard Rigid VentingCheck GAS Type Fireplace InstallationInstalling Optional Blower Accessory Installing GA3700/DA3610T BlowersSide View As a freestanding unit with an acInstallation Items Needed Installing GAS Piping to Fireplace LocationTest Pressures In Excess Of 1/2 Psig 3.5 kPa Connecting Fireplace to GAS SupplyPressure Testing Gas Supply Piping System Checking GAS ConnectionsInstalling Optional Wall Mount Switch GWMS2 Pressure Testing Fireplace Gas ConnectionsTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Installing Remote Receiver Installing 9-Volt Battery in Hand- Held Remote Control UnitREMOVING/REPLACING Glass Door Installing Left Side Brick Panel Installing Optional Brick Liner D8037Fireplace Models BDV34NA and BDV34PA Installing LOGS, Lava Rock and Glowing EmbersLighting Instructions For Your Safety Read Before LightingManual Lighting Procedure Operating FireplaceOptional Remote Operation Operating Optional Blower AccessoryPilot Assembly Inspecting BurnersCleaning and Maintenance Observed Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Above Gas leak. See Warning statementParts Under Warranty Replacement Wiring Diagram PartsTechnical Service Service HintsBDV34NA BDV34PA SpecificationsAccessories Brass Louver KIT Receiver and HAND-HELD Remote Control KIT Ghrc SeriesON/OFF Wall Mount Switch GWMS2 Duplex Outlet KIT GA3555 not ShownIllustrated PARTS37 Breakdown DIRECT-VENT Fireplace BDV34NA Parts ListBDV34PA7 DIRECT-VENT Fireplace BDV34PA Warranty Information