12
INSTALLATION
INSTALLATION
Continued
Mantel Clearances for Built-In Installation
If placing mantel above
NOTICE: If your installation does not meet the mini- mum clearances shown, you must do one of the following:
•raise the mantel to an acceptable height
•remove the mantel
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNING: This appliance requires a 1/2" NPT (National Pipe Thread) inlet connection to the pres- sure regulator.
WARNING: A qualified service person must con- nect fireplace to gas supply. Follow all local codes.
CAUTION: Never connect propane/LP fireplace directly to the propane/LP supply. This fireplace requires an external regulator (not supplied). Install the external regulator between the fireplace and pro- pane/LP supply.
Wall board or facing material (above firebox) may be of
Mantel Shelf
WARNING: Never connect natural gas fireplace to private
combustible material, including decorative mantel ornaments or other similar projec- tions off of the facing material.
Framing
Material
Firebox
Screen
10"
8"
6"
21/2"
Noncombustible Material May Project Off this Surface above the Firebox Hood
Supplied Firebox
Hood Must Be
Used at All Times
13" 16" 19" 21"
Note: All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf.
These minimum clearances replace any other recommended clearances supplied with your ANSI Z21.11.2 approved gas logs.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
•external regulator for propane/LP unit only (supplied by installer)
•piping (check local codes)
•sealant (resistant to propane/LP gas)
•equipment shutoff valve *
•test gauge connection *
•sediment trap (optional)
•tee joint
•pipe wrench
•approved flexible gas line with gas connector (if allowed by lo- cal codes) (not provided)
*A CSA
Figure 20 - Minimum Mantel Clearances for Built-In Installation
For propane/LP units, the installer must supply an external regula- tor. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent point- ing down as shown in Figure 21, page 13. Pointing the vent down protects it from freezing rain or sleet.