LG Electronics LGxxxA1C-B3 manual Checking for Interferences to the Power Line Communication

Page 17

3-1-6 Checking for Interferences to the Power Line Communication

If there is still a problem with the connection between the gateway and the AC module, it is necessary to check the factors causing interference.

First, connect the gateway directly to the AC module. This will eliminate any potential interference caused by other devices; normal communication should be achieved and the AC modules should be detectable by the smart phone app.

If the AC modules are still not detected on the app, there could be a communication problem between the smart phone/tablet and the gateway. If you suspect that there is a problem with the gateway, please request for a replacement unit.

It is recommended to install the gateway as illustrated in the figure below to prevent communication interferences.

PV Rack

AC Module

Trunk Cable

Transition Cable

 

 

 

 

 

 

AC Junction Box

 

 

 

 

Equipment

 

 

 

 

 

Grounding

General AC

 

 

 

 

Conductor

 

 

 

 

Cable

 

 

 

 

 

 

 

 

 

 

Communication

Meter

 

 

 

 

0 0 0 0 0

 

 

 

 

Gateway

 

 

 

 

 

Sub Panel

 

 

Installation App

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

N L1L2

 

 

 

120VAC

Distribution Panel

 

 

 

 

If normal communication between the gateway and the AC module is established, close all the circuit breakers except for that of the gateway and the AC module. Disconnect the gateway from the AC module and re-install it indoors.

Verify that the connection between the gateway and AC module is maintained after the second installation. The correct number of AC modules should now be visible from the app.

Turn on one of the circuit breakers and wait 10 to 15 minutes. Scan for the AC modules through the app. If successful, turn on another circuit breaker and scan for the AC modules. Repeat until all circuit breakers are back on. If you encounter an error while scanning, the last circuit breaker is interfering with the communication.

17

Image 17
Contents Troubleshooting Guide AC module Product SpecificationsDimension Dedicated Cables Response to Abnormal ConditionsParameter Range Clearing Time s Table of Contents Safety Symbols SafetyGateway Ex App Messages Screen Messages and AlertsDate AC module ID Message type Ex Web Array View ScreenApp Message Screen Ex Web Event ScreenEx Voltage Low Screen X12 An array of AC modules Ex AC Frequency Low Ex Frequency Changing Too Fast ScreenNominal Frequency 60Hz 59.3 to 60.5Hz Hawaii 57 to 60.5Hz Error #2 DC Current High Error #1 DC Voltage HighEx DC Voltage High Screen Ex DC Current High ScreenError #4 Inverter Failure Error #3 AC Current HighEx AC Current High Screen Ex Inverter Failure ScreenEx Temperature Protection Screen Error #5 Temperature ProtectionAlert Gfdi Ex Gfdi ScreenFactors that Affect Power Line Communication Gateway and Communication IssuesProblems Checking AC Module through the Smartphone App Checking for Interferences to the Power Line Communication Solving Connection Issues in the Gateway Connecting the Gateway to a Remote RouterChanging the EnerBox Registering Additional AC Modules to the GatewayRelocating a Gateway with Completed AC Module Registration Registering a Replacement AC Module to the GatewayNetwork Configuration Troubleshooting Memo Memo