Ex) Web Event Screen
1Current Issues : Provides the current conditions of the system.
2Event History : Provides the event records for aspecified period.
3Click the device in the query results to check the “Issue Details”. A
Affected devices, alert type, alert duration and detailed descriptions.
Notice #1 and #2 AC Voltage High/ Low
•It occurs when the system voltage is lower or higher than the operational threshold. Due to a problem of the power company, it can temporarily happen or and it is automatically adjusted by the power company. If the problem persists, check the followings.
Nominal Voltage 240 Volt AC | Nominal Voltage 208 Volt AC | ||
L1, L2 to neutral | 106 to 132 Vac | L1, L2, L3 to neutral | 106 to 132 Vac |
L1 to L2 | 211 to 264 Vac | L1 to L2 to L3 | 183 to 229 Vac |
Ex) Voltage Low Screen
App Message Screen | Web Event Screen |
•Check the voltage at terminals in the distribution
9