LG Electronics LGxxxA1C-B3 manual Response to Abnormal Conditions, Parameter Range Clearing Time s

Page 4

Response to Abnormal Conditions

IEEE 1547 (Default)

Parameter

Range

Clearing Time (s)

Phase Voltage

V < 60V

<0.16

 

 

 

 

60V ≤ V < 106V

< 2.00

 

 

 

Voltage

132 ≤ V < 144V

< 1.00

 

 

 

 

V ≥ 144V

< 0.16 (< 0.016, Hawaii mode - TOV)1)

Frequency

> 60.5Hz

< 0.16

 

 

< 59.3Hz (< 57 Hz, Hawaii mode)1)

< 0.16

 

Note 1 : This test is performed in nominal conditions, except for test parameter

Note 2 : After clearing, if grid returns to the normal state, it takes up to 5 minutes for operation of AC module

Dedicated Cables

 

Trunk

 

Type

 

TC-ER sunlight resistant

Max. Voltage

 

600V

Cable

 

20A

Max. Current

 

Size

 

12AWG

Max. Voltage

 

300V

Connector

 

20A

Max. Current

 

 

Drop

 

Type

 

TC-ER sunlight resistant

Max. Voltage

 

600V

Cable

 

5A

Max. Current

 

Size

 

18AWG

Max. Voltage

 

300V

Connector

 

5A

Max. Current

 

 

Certification

 

UL9703, UL6703A

 

 

Dimensions

 

400 mm

 

(95.75 inch)

 

53 mm

31.5 mm

 

(2.09 inch)

(1.24 inch)

 

122 mm

 

 

(4.80 inch)

1,200 mm

66 mm

 

(47.24 inch)

(2.60 inch)

4

 

 

Image 4
Contents Troubleshooting Guide Product Specifications AC moduleDimension Parameter Range Clearing Time s Response to Abnormal ConditionsDedicated Cables Table of Contents Safety Safety SymbolsGateway Messages and Alerts Ex App Messages ScreenDate AC module ID Message type Ex Web Array View ScreenEx Voltage Low Screen Ex Web Event ScreenApp Message Screen X12 An array of AC modules Nominal Frequency 60Hz 59.3 to 60.5Hz Hawaii 57 to 60.5Hz Ex Frequency Changing Too Fast ScreenEx AC Frequency Low Error #1 DC Voltage High Error #2 DC Current HighEx DC Voltage High Screen Ex DC Current High ScreenError #3 AC Current High Error #4 Inverter FailureEx AC Current High Screen Ex Inverter Failure ScreenError #5 Temperature Protection Ex Temperature Protection ScreenAlert Gfdi Ex Gfdi ScreenGateway and Communication Issues Factors that Affect Power Line CommunicationProblems Checking AC Module through the Smartphone App Checking for Interferences to the Power Line Communication Connecting the Gateway to a Remote Router Solving Connection Issues in the GatewayRegistering Additional AC Modules to the Gateway Changing the EnerBoxRegistering a Replacement AC Module to the Gateway Relocating a Gateway with Completed AC Module RegistrationNetwork Configuration Troubleshooting Memo Memo