Delta instruction sheet DT3 Series Temperature Controller Instruction Sheet

Page 1

DT3 Series Temperature Controller Instruction Sheet

Precaution

DANGER! Caution! Electric Shock!

1.Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.

2.Make sure power is disconnected while checking the unit inside.

WARNING!

This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a serious human injury or serious property damage may occur.

1.Always use recommended solder-less terminals: Fork terminal with isolation. (M3 screw, width is 6.0mm)

2.Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.

3.Never modify or disassemble the controller.

4.Do not connect anything to the “No used” terminals.

5.Make sure all wires are connected to the correct polarity of terminals.

6.Do not install and/or use the controller in places subject to:

y Dust or corrosive gases and liquid

y High humidity and high radiation

y Vibration and shock

y High voltage and high frequency

7.Must turn power off when wiring and changing a temperature sensor.

8.Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.

9.Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).

10.Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise.

11.This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials, airborne dust and electric shock or vibration.

12.Please make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur.

13.Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric shock.

14.Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit within this period.

15.Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.

Display, LED & Pushbuttons

Odering Information

 

DT3 Series

DT3: Delta 3 Series Temperature Controller

 

 

 

 

20: 4848 1/16 DIN W48 × H48mm

 

40: 4896 1/8 DIN W48 × H96mm

 

Panel Size (W×H)

 

30: 7272 W72 × H72mm

 

60: 9696 1/4 DIN W96 × H96mm

 

 

 

R: Relay Output, 250 VAC, 5A

 

 

1st output group selection

 

V: Voltage Pulse Output, 12V ±10%

 

 

 

C: DC Current Output, 4 ~ 20 mA

 

 

 

 

 

 

 

 

L: Linear Voltage Ouptut 0 ~ 10 VDC

 

 

Power supply

 

A: AC 80 ~ 260 V

 

 

 

D: DC 24 VDC

 

 

 

 

 

 

2nd output group selection

 

0: None

 

 

 

R: Relay Outupt,250 VAC, 5A

 

 

 

 

 

1

Image 1
Contents Display, LED & Pushbuttons Odering Information DT3 Series Temperature Controller Instruction SheetRUN OperationOFF Cons PIDAscii MA4TUNE=AT END Stop = 1mVDisplay Unit Setting Initial Start-up SettingSet Value and the Upper/Lower Limit of Input Value Setting Digital Filter and Linear Compensation SettingRetransmission and Compensation Adjusting Disable the Cold Junction FunctionApplications of Analog Voltage & Current Input Analog Output CompensationCheck the Firmware Version and Output Type Selection for Heating/Cooling/Alarm/Dual Loop Output ControlSV Control Mode Setting Page IOF Control Mode SettingSetting of multiple PID sets Set Reverse Output Tune FunctionLimits controlling the output range CT FunctionUser Setting of F1, F2 function keys Limits of temperature rangesEvent Function Edit a self-defined Menu ScreenKey Lock Function Restore Factory SettingsAL-H Alarm OutputsRS-485 Communication 999 ~ 9,999 Programmable Waiting Setting range 0~1000100.0 Temeprature ADR STXCMD LRCPanel Cutout