Delta DT3 instruction sheet 999 ~ 9,999

Page 18

1006H

Heating/Cooling control selection

Refer to Ouputput Mode Selection

 

 

 

1007H

1st group of Heating/Cooling

1~990, unit is 0.1 second. When the output setting = realy, the minimum control

 

control cycle

cycle is 5 second

1008H

2nd group of Heating/Cooling

1~990, unit is 0.1 second. When the output setting = realy, the minimum control

 

control cycle

cycle is 5 second 1~990

1009H

PB Proportional band

0.1 ~ 999.9

100AH

Ti Integral time

0~9,999

100BH

Td Derivative time

0~9,999

 

 

 

100CH

Integration default

0 ~ 100%, unit is 0.1%

 

 

 

100DH

Proportional control offset error

0 ~ 100%, unit is 0.1%

 

value, when Ti=0

 

 

100EH

The setting of COEF when Dual

0.01 ~99.99, unit is 0.01

 

Loop output control are used

 

100FH

The setting of Dead Band when

-999 ~ 9,999

 

Dual Loop output control are

 

 

used

 

1010H

Hysteresis setting value of the

0~9,999

 

1st output group

 

1011H

Hysteresis setting value of the

0~9,999

 

2nd output group

 

1012H

Output value read and write of

Unit is 0.1%, write operation is valid under manual tuning mode only.

 

Output 1

 

 

1013H

Output value read and write of

Unit is 0.1%, write operation is valid under manual tuning mode only.

 

Output 2

 

 

1016H

Temperature regulation value

-99.9 ~ +99.9. Unit is 0.1

 

 

 

1017H

Analog decimal setting

0 ~ 3

101CH

PID parameter selection

0~5/AUTO

101DH

SV value corresponded to PID

Only valid within available range, unit: 0.1 scale

 

value

 

 

1020H

Alarm 1 type

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1021H

Alarm 2 type

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1022H

Alarm 3 type

Please refer to the contents of the “Alarm Outputs” for detail

1024H

Upper-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1025H

Lower-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1026H

Upper-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1027H

Lower-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1028H

Upper-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1029H

Lower-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

102AH

Read LED Status

b0: ALM3, b1: ALM2, b2: , b3: , b4: ALM1, b5: OUT2, b6:OUT1, b7: AT

102BH

Read Pushbutton Status

b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key

102CH

Setting lock status

 

 

 

 

102FH

Software version

V1.00 indicates 0x100

 

 

 

1030H

Start pattern number

0 ~ 15

 

Pattern 0~15 temperature set

-999 ~ 9999

1200H~13FFH

point setting (Even number)

Pattern 0~15 execution time

Time: 0 ~ 9001 minute per scale

 

 

setting (Odd number)

 

1400H~140FH

Actual number of step setting

0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N

inside the corresponding pattern

 

 

 

Cycle number for repeating the

 

1410H~141FH

execution of the correspond

0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times

 

pattern

 

1420H~142FH

Link pattern number setting of

0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the

program end and execution end. 0~15 indicates the next execution pattern

the correspond pattern

 

number after executing the current pattern

 

 

 

 

 

 

 

 

Address

Content

Definition

1100H

Adjust Temperature Gain

 

 

 

 

1101H

Temperature Filter Range

Range of temperature filter: 10~1000, unit: 0.01 , default: 100(1.0)

1102H

Temperature Filter Factor

Setting range: 0~50, default: 8

18

Image 18
Contents DT3 Series Temperature Controller Instruction Sheet Display, LED & Pushbuttons Odering InformationOperation RUNOFF PID ConsMA4 AsciiTUNE=AT = 1mV END StopSet Value and the Upper/Lower Limit of Input Value Setting Initial Start-up SettingDisplay Unit Setting Digital Filter and Linear Compensation SettingApplications of Analog Voltage & Current Input Disable the Cold Junction FunctionRetransmission and Compensation Adjusting Analog Output CompensationSelection for Heating/Cooling/Alarm/Dual Loop Output Control Check the Firmware Version and Output TypeSV Control Mode Setting Page Control Mode Setting IOFSetting of multiple PID sets Limits controlling the output range Tune FunctionSet Reverse Output CT FunctionEvent Function Limits of temperature rangesUser Setting of F1, F2 function keys Edit a self-defined Menu ScreenRestore Factory Settings Key Lock FunctionAlarm Outputs AL-HRS-485 Communication 999 ~ 9,999 Programmable Waiting Setting range 0~1000100.0 Temeprature CMD STXADR LRCPanel Cutout