Delta DT3 instruction sheet Operation, Run, Off

Page 2

V:Voltage Pulse Output, 12V ±10%

C:DC Current Output 4 ~ 20 m A

L:Linear Voltage Ouptut 0 ~ 10 VDC

EVENT inputs/ CT function (optional) 1 0: None, 1: Event Input3, 2: RS-485 Communication

EVENT inputs/ CT function (optional) 2 0: None, 1: Event Input2, 2: CT measure input2, 3: Retransmission Output

EVENT inputs/ CT function (optional) 3 0: None, 1: Event Input1, 2: CT measure input1, 3: Remote Setpoint input

Specifications

Input Voltage

AC 80 ~ 260 V, 50/60Hz; DC24 VDC ±10%

Power Consumption

5VA max.

Display Method

LCD display. Process value (PV): Yellow color, Set point (SV): Green color

 

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK

Sensor Type

3-wire Platinum RTD: Pt100, JPt100

 

 

 

Analog input: 0 ~ 5 V, 0 ~ 10 V, 0 ~ 20 m A, 4 ~ 20 mA, 0 ~ 50 mV

Control Mode

PID, PID program control (Ramp/Soak control), FUZZY, Self-tuning, Manual and On/FF

 

 

Relay output: Max. load 250VAC, 5A resistive load

 

 

Control Output

Voltage pulse output: DC 12V, Max. output current 40mA

 

Current output: DC 4 ~ 20m A output (Load resistance: Max. 500Ω)

 

 

Analog voltage output: 0 ~ 10V

Warning Output Type

Relay output: Max. load 250VAC, 3A resistive load

Display Accuracy

0 or 1 digit to the right of the decimal point (selectable)

Sampling Rate

Analog input: 0.1 sec/ per scan; Thermocouple or Platinum RTD: 0.1 sec/per scan

Vibration Resistance

10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions

Shock Resistance

Max. 300m/ s2, 3 times in each 3 axes, 6 directions

Ambient Temperature

0°C ~ +50°C

Storage Temperature

-20°C ~ +65°C

Altitude

Max. 2000m

Relative Humidity

35% ~ 80% RHnon-condensing

 

 

Operation

™There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation

mode. Press the key to switch to regulation mode. If the key is pressed for more than 3 seconds, controller will switch to the

initial setting mode. Pressing the key while in the regulation mode or initial setting mode, forces the controller to return to the operation mode..

™PV/SV: Sets the temperature set point and displays the temperature process value. Use keys to set the temperature set point.

™Setting method: While in any function mode, press the key to select the desired function and use keys to change

settings. Press key to save the changes.

™The flow chart below shows how to switch the settings and internal functions:

Regulation Mode

Press key less than 3 sec

Press key

Operation Mode

Press key more than 3 sec

Press key

Initial Setting Mode

Operation ModeParameter Setting:

Display

 

Description

Factory Setting

 

Use

to set temperature set point, use

to switch between the display parameter

 

 

RUN/STOP: Control setting RUN or STOP

 

RUN

 

 

 

 

PATTERN: Start pattern setting (set control mode to PROG mode)

0

 

STEP: Start step setting (set control mode to PROG mode)

0

 

 

 

 

SELECT POINT: Decimal point setting (0: integral ; 1: one decimal point)

1

 

LOCK: Setting lock mode (LOCK1: all; LOCK2: onlySV and F1/F2 key is allowed)

OFF

 

 

 

 

ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode)

4.0

2

Image 2
Contents DT3 Series Temperature Controller Instruction Sheet Display, LED & Pushbuttons Odering InformationOFF OperationRUN PID ConsTUNE=AT MA4Ascii = 1mV END StopSet Value and the Upper/Lower Limit of Input Value Setting Initial Start-up SettingDisplay Unit Setting Digital Filter and Linear Compensation SettingApplications of Analog Voltage & Current Input Disable the Cold Junction FunctionRetransmission and Compensation Adjusting Analog Output CompensationSelection for Heating/Cooling/Alarm/Dual Loop Output Control Check the Firmware Version and Output TypeSV Control Mode Setting Page Control Mode Setting IOFSetting of multiple PID sets Limits controlling the output range Tune FunctionSet Reverse Output CT FunctionEvent Function Limits of temperature rangesUser Setting of F1, F2 function keys Edit a self-defined Menu ScreenRestore Factory Settings Key Lock FunctionAlarm Outputs AL-HRS-485 Communication 999 ~ 9,999 Programmable Waiting Setting range 0~1000100.0 Temeprature CMD STXADR LRCPanel Cutout