Delta DT3 instruction sheet SV Control Mode Setting

Page 9

Output of when in PID control mode (Ctrl=PID):

Heating

Cooling

Heating

Cooling

 

 

Set Point

Set Point

When the controller is in PID control and dual loop output mode, sets the P value of the 2nd set of PID. The 1st set of PID is generated when TUNE= AT, but user can also manually sets the PID value. The P value of th 2nd set of PID = the P value of 1st

set of PID x . The I and D value of the 2nd set of PID remains the same as the 1st set of PID.

SV Control Mode Setting

There are 4 methods for setting SV of the temperature setting; they are Fixed, Slope, Program and Remote.

zFixed SV Mode: controls the temperature to directly rise to a fixed setting value

¾Set parameter to in Initial Setting Mode

¾Set the target temperature: set SV value by a parameter in Operation Mode

zSlope SV Mode: Control temperature rises at a slope (unit: /min.) to a fixed value, i.e., the temperature can be set to rise in a

set slope (unit: /min.). E.G., Set a slope of 0.5 and set SV to 200.0; this means the temperature rises 0.5every minute from Room Temperature up to 200.0.

¾Set parameter to in Initial Setting Mode

¾Set rising slope (unit: /min. or /s): set rising slope by parameter in Regulation Mode

¾Set target temperature: set SV value by a parameter in Operation Mode

¾Set unit for rising slope (unit: /min. or /s): for parameter in Initial Setting Mode, set the corresponding Y

position value to xxYx (Y can be 0 or 1; Y= 0: /min.; Y=1: /s).

zProgram SV mode: This means the temperature setting value is not a fixed value but a setting curve defined by the user according to his-her requirements. By way of PID control, the temperature input rises along with the defined temperature curve. As to how to input the temperature setting curve, the machine provides 16 patterns with 16 steps each, together with a linking parameter, a loop parameter, and a number of executions. Each step has 2 parameters (temperature setting value and time). If the initial step has a time parameter set to 0, temperature will rise from room temperature at the initial slope up to the target temperature. After setting these parameters, each temperature controller will have its own set of initial pattern and initial step for creating its own temperature setting curve. Some of the terms are explained as follows:

aInitial pattern: set the program to start running at a sequential number of patterns

bInitial Step: set the program to start running at a sequential number of steps

cInitial Slope: If the time setting of the initial step of the initial pattern is set to 0, an initial slope shall be set to allow the temperature to rise from room temperature to the setting value.

dStep: includes 2 parameter settings: a setting point X and an executing time T, representing the setting value (SV) to rise to X after time T. If the setting point X is identical to the previous setting, this process is called a Soak, otherwise a Ramp, therefore this control procedure is also called a Ramp Soak control. The first running procedure is preset as a Soak control, to set the temperature control to setting point X in advance and maintain the temperature at X, at a duration of T.

eLink Parameter: the number of the subsequent pattern to be linked after executing this pattern. If set to END, the program mode will end but maintain the last setting value; if set to STOP, all the program controls will end with the output switched off.

fNumber of loops: Number of extra loops to be carried out for the pattern. If set to 1, the pattern will be carried out 2 times.

gExecuting step: Number of steps executed for each pattern.

hWait time, wait temperature: After reaching the program temperature value, a wait time and wait temperature can be set; if the current temperature is not within the range of (temperature setting value ± wait temperature), the set wait time will start to count down until the currently measured temperature reaches the range of (temperature setting value ± wait temperature) of each step before proceeding to the subsequent step. An alarm will be issued if the range of (temperature setting value ± wait temperature) is not reached when the count down reaches 0.

iExecution:

9

Image 9
Contents Display, LED & Pushbuttons Odering Information DT3 Series Temperature Controller Instruction SheetOperation RUNOFF Cons PIDMA4 AsciiTUNE=AT END Stop = 1mVDisplay Unit Setting Initial Start-up SettingSet Value and the Upper/Lower Limit of Input Value Setting Digital Filter and Linear Compensation SettingRetransmission and Compensation Adjusting Disable the Cold Junction FunctionApplications of Analog Voltage & Current Input Analog Output CompensationCheck the Firmware Version and Output Type Selection for Heating/Cooling/Alarm/Dual Loop Output ControlSV Control Mode Setting Page IOF Control Mode SettingSetting of multiple PID sets Set Reverse Output Tune FunctionLimits controlling the output range CT FunctionUser Setting of F1, F2 function keys Limits of temperature rangesEvent Function Edit a self-defined Menu ScreenKey Lock Function Restore Factory SettingsAL-H Alarm OutputsRS-485 Communication 999 ~ 9,999 Programmable Waiting Setting range 0~1000100.0 Temeprature ADR STXCMD LRCPanel Cutout