Delta DT3 Event Function, Limits of temperature ranges, User Setting of F1, F2 function keys

Page 14

EVENT Function

This controller provides a maximum of 3 EVENTs (EV1~EV3) for respectively setting EV functions as shown in the following Table <1>. For example, if EV1 is used for Run/Stop selection, when the controller is set to RUN status, if terminals in the Option1 slot are open, the controller is in RUN status; if terminals in the Option1 slot are shorted, the controller switches to STOP status.

Function setting

0

1

2

 

3

4

Function

Disable

Run/Stop

SV 1/ SV 2

 

Auto/

Run/ Hold

 

Manual

 

 

 

 

 

 

 

Table <1> EVT function setting

 

 

Run/Stop: This function switches the controller between RUN and STOP status.

SV 1/SV 2: This function selects SV 1 or SV 2 as the active setpoint.

Auto/Manual: This function selects PID and Manual control.

Run/Hold: This function switches controller between run and hold status when in program control.

¾Insert EV1, EV2 PCB to Option1 or Option2, or insert hardware with a built-in EV3 function

¾Set EV functions as listed in Table <1> EVT Function Setting by parameters , , inRegulation Mode. Note: Selection of “Evt‘x’” items must match with the inserted PCB; if only Option1 is inserted, then only “Evt1” will be displayed.

Limits of temperature ranges

Different input sensors have different application ranges (e.g.: J type factory setting is -100 ~ 1200), adjust parameters

(upper

limit) /

(lower limit) in Initial Setting Mode.

 

If lower limit is altered to 0 and upper limit is altered to 200, the limit function will be enabled in the following conditions:

 

¾When setting the SV value, the limits may set for 0~200

¾In ON-OFF, PID, FUZZY and Self-Tuning control conditions, the control output will be forced to shut off if the PV value exceeds the upper/lower limit. (Alarm output is still normal)

User Setting of F1, F2 function keys

In the Operation Mode, (PV/SV display mode), pressing a function key more than 3 seconds will prompt you to the setting of the following

functions; press keys to make a selection.

Function

 

Description

 

When in a screen other than the PV/SV display mode, pressing F1/F2 key continuously may save the setting, to quickly

MENU

switch the menu screen

 

 

(When the screen shows KEY SAVE, the menu screen is saved)

AT

Selecting this function, F1 / F2 button can be used for quick ON / OFF operation of AT function

R-S

Selecting this function, F1

/ F2 button can be used to switch between RUN/STOP status.

 

 

 

PROG

Selecting this function, F1

/ F2 button can be used to switch between RUN/HOLD status.

 

 

 

ATMT

Selecting this function, F1

/ F2 button can be used to switch between PID and MANUAL control mode

For disabling F1/F2 function, please select MENUwithout saving any menu screen.

Edit a self-defined Menu Screen

Hidden MENU setting: Lock all buttons by adjusting parameter to in Operation Mode. At the same time press

and keys for 3 seconds to display , and enter Password-1. The screen will show menu number , see the following table for details. Select “Hide” to hide the Menu.

Menu Layer setting: Lock all buttons by adjusting parameter to in Operation Mode. At the same time press

and keys for 3 seconds to display , and enter Password-2. The screen will show menu number , see the following table for details. Selectable items are NOR= display layers; ADJ= adjust layers; SET= set layers.

Menu layer reset: Lock all buttons by adjusting parameter

to

in Operation Mode. At the same time press

and

keys for 3 seconds to display

, and enter Password-3. The screen displays

(Level reset) parameters, select

to reset all menu layers to default setting.

 

 

 

 

 

RUN layer

 

Adjust layer

Menu No.

 

Corresponding menu

Menu No.

 

Corresponding menu

M101

 

 

M201

 

 

 

 

 

 

 

 

M102

 

 

M202

 

 

 

 

 

 

 

 

Setting layer

Menu No.

 

Corresponding menu

M301

 

 

M302

 

 

 

 

 

 

 

14

Image 14
Contents DT3 Series Temperature Controller Instruction Sheet Display, LED & Pushbuttons Odering InformationOFF OperationRUN PID ConsTUNE=AT MA4Ascii = 1mV END StopSet Value and the Upper/Lower Limit of Input Value Setting Initial Start-up SettingDisplay Unit Setting Digital Filter and Linear Compensation SettingApplications of Analog Voltage & Current Input Disable the Cold Junction FunctionRetransmission and Compensation Adjusting Analog Output CompensationSelection for Heating/Cooling/Alarm/Dual Loop Output Control Check the Firmware Version and Output TypeSV Control Mode Setting Page Control Mode Setting IOFSetting of multiple PID sets Limits controlling the output range Tune FunctionSet Reverse Output CT FunctionEvent Function Limits of temperature rangesUser Setting of F1, F2 function keys Edit a self-defined Menu ScreenRestore Factory Settings Key Lock FunctionAlarm Outputs AL-HRS-485 Communication 999 ~ 9,999 Programmable Waiting Setting range 0~1000100.0 Temeprature CMD STXADR LRCPanel Cutout