Delta DT3 instruction sheet Programmable Waiting Setting range 0~1000100.0 Temeprature

Page 19

1103H

Reverse Output

Bit1: output 2, Bit0: output 1

 

 

 

1104H

Slope of Temperature Increase

Unit: 0.1/min or 0.1/sec (refer to CommunicationAddress 1124H)

1105H

Remote Input Type Selection

0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V

1106H

AT Control

0: AT(Auto-tune), 1: ST(Self-tune)

 

 

 

1107H

Remote Input Reverse Setting

0: forward, 1: reverse

 

 

 

1108H

Alarm 1 Function Selection

Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable

1109H

Alarm 2 Function Selection

Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable

110AH

Alarm 3 Function Selection

Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable

 

 

 

110BH

Alarm 1 Output Delay Time

Unit: second. Setting range: 0~100sec

 

 

 

110CH

Alarm 2 Output Delay Time

Unit: second. Setting range: 0~100sec

110DH

Alarm 3 Output Delay Time

Unit: second. Setting range: 0~100sec

110EH

Upper Limit of Control Output 1

Range: lower limit of control output ~100%, unit is 0.1%

 

 

 

110FH

Lower Limit of Control Output 1

Range: 0~upper limit of control output, unit is 0.1%

1110H

Upper Limit of Control Output 2

Range: lower limit of control output~100%, unit is 0.1%

1111H

Lower Limit of Control Output 2

Range: 0~upper limit of control output, unit is 0.1%

 

 

 

1112H

Programmable Waiting

Setting range: 0~1000(100.0)

 

Temeprature

 

1113H

Programmable Waiting Time

Unit: min. Setting range: 0~900

 

 

 

1114H

Programmable Slope Increase

Unit: 0.1/min or 0.1/sec--- (refer to Communication Address 1124H) Setting

 

 

range: 0~1000

1115H

Testing Mode

 

1116H

Adjust Upper Limit of Analog

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

 

Linear Output 1

 

1117H

Adjust Lower Limit of Analog

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

 

Linear Output 1

 

1118H

Adjust Upper Limit of Analog

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

 

Linear Output 2

 

1119H

Adjust Lower Limit of Analog

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

 

Linear Output 2

 

111AH

Adjust Retransmission Upper

Adjust current: 1scale=1μA

 

Limit

 

111BH

Adjust Retransmission Lower

Adjust current: 1scale=1μA

 

Limit

 

111CH

Event 1 Selection

0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to

 

 

Programmable Hold mode

111DH

Event 2 Selection

0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to

 

 

Programmable Hold mode

111EH

Event 3 Selection

0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to

 

 

Programmable Hold mode

111FH

PV Control Mode Selection

0: PID, 1: ON/OFF, 2: Manual control, 3: Fuzzy

1120H

SV Control Mode Selection

0: Constant, 1: Slope increase, 2: Programmable input, 3: Remote Input

 

 

 

1121H

Adjust Remote Compensation

Setting range: -999~999

 

 

 

1122H

Adjust Remote Gain

Setting range: -999~999

1123H

Positive/Negative Selection for

0: Positive, 1: Negative

 

Remote

 

 

 

 

1124H

Switch Slope Time Unit

0: min, 1: sec

1125H

Cold Junction Compensation

0: ON, 1: OFF

1126H

Reserve the Programmable

0: None, 1: Running status is saved and will continue by the previous status when

 

Running Status when Power OFF

power ON.

1127H

Fuzzy Gain

Setting range: 1~10

 

 

 

1128H

Fuzzy Dead Band

Setting range: 0.0~PB

 

 

 

1129H

Save Programmable Settings

0:None, 1: Saves the programmable settings into memory

 

into Memory

 

1182H

CT1 Read Value

Unit: 0.1A

1183H

CT2 Read Value

Unit: 0.1A

1. Address and Content of Bit Register: First bit of reading will put into LSB. Write data= FF00H for bit set, 0000H for bit clear.

0810H

Read AT LED status

0: OFF(default), 1: ON

0811H

Temperature unit display

0: , 1: / linear input (default)

19

Image 19
Contents Display, LED & Pushbuttons Odering Information DT3 Series Temperature Controller Instruction SheetRUN OperationOFF Cons PIDAscii MA4TUNE=AT END Stop = 1mVDigital Filter and Linear Compensation Setting Initial Start-up SettingDisplay Unit Setting Set Value and the Upper/Lower Limit of Input Value SettingAnalog Output Compensation Disable the Cold Junction FunctionRetransmission and Compensation Adjusting Applications of Analog Voltage & Current InputCheck the Firmware Version and Output Type Selection for Heating/Cooling/Alarm/Dual Loop Output ControlSV Control Mode Setting Page IOF Control Mode SettingSetting of multiple PID sets CT Function Tune FunctionSet Reverse Output Limits controlling the output rangeEdit a self-defined Menu Screen Limits of temperature rangesUser Setting of F1, F2 function keys Event FunctionKey Lock Function Restore Factory SettingsAL-H Alarm OutputsRS-485 Communication 999 ~ 9,999 Programmable Waiting Setting range 0~1000100.0 Temeprature LRC STXADR CMDPanel Cutout