¾Remote compensation adjustment: input corresponding lower limit of analog signal at the Remote end, set Remote
compensation adjustment by parameter in【Regulation Mode】
¾Remote gain adjustment: input corresponding upper limit of analog signal at the Remote end, set Remote compensation
adjustment by parameter in【Regulation Mode】
¾Remote lower limit: Setting Remote lower limit by parameter in【Regulation Mode】
¾Remote higher limit: Setting Remote higher limit by parameter in【Regulation Mode】
Control Mode Setting
There are 4 control modes;
z
Heating sensitivity | Cooling sensitivity |
adjustment | adjustment |
| DeadBand |
HeatingCooling
Set value
(Output
¾Set parameter to in 【Initial Setting Mode】
¾Set adjustment sensitivity: Set adjustment sensitivity by parameter【Regulation Mode】 to (Output 1), (output 2)
¾Setting of DeadBand of both outputs: Set DeadBand by parameter in 【Regulation Mode】
zPID Mode: When set for heating or cooling, the program performs PID operation via input temperature and setting temperature, with the operation result output for the temperature control. A PID parameter and control period must be set for this function; these parameters can also be generated automatically via
a、 A total of six sets of PID parameters are available, one of which can be selected for carrying out PID, and the program may automatically select a set of PID that is most close to the input value. In order to achieve this, each set of PID parameters has a reference input setting value which allows the user to set for manual setting or for
| 0 | 1 | 2 | 3 | 4 | 5 |
SV | 80 | 160 | 240 | 320 | 400 | 480 |
P | 120 | 46 | 70 | 60 | 40 | 50 |
I | 100 | 140 | 180 | 200 | 220 | 240 |
D | 25 | 35 | 45 | 50 | 55 | 60 |
IOF | 20 | 10 | 30 | 20 | 30 | 21 |
|
|
|
|
|
|
|
b、 Set PID parameters and the control period: in which PID parameters can be adjusted manually according to system characteristics or created automatically by AT, the
achieving the setting value; unit is % output; proportional error compensation is: when I parameter is set to =0, for the adjustment of reduced time to reach the temperature. The Control Period is the period of PID operation, if the control period is 10s, it means a PID operation is carried out every 10s. The result is then output to control the temperature. If the system heats up quickly, the control period shall not be set too long. For relay output, the lifespan of the relay shall be considered; a short period will shorten the lifespan of relay.