Emerson iCOM Digital Scroll High Temperature, Compressor Timing-Units With Two Compressors

Page 21

Operation

Digital Scroll High Temperature

A protective maximum operating compressor temperature limit is imposed on units with digital scroll compressor(s) with thermistor. Once the digital scroll temperature reaches the maximum tempera- ture threshold, the compressor will be locked out for at least 30 minutes and an alarm will be annun- ciated. If after 30 minutes the temperature has cooled to a safe operating temperature, the compressor will resume operation.

Each time a high-temperature alarm occurs, HT 1 Alarm Counter (Service Menu, Diagnostics) or HT 2 Alarm Counter (Service Menu, Diagnostics) is increased by one. Once these counters reach five occurrences in a rolling four-hour period, the compressor will be locked out. The alarm can be reset once the temperature returns to a safe level by:

1.Setting the counter back to 0 from the display and pressing the alarm reset button.

2.Shutting off power to the control board by turning the cooling unit's main power disconnect switch Off and On.

3.1.4Compressor Timing—Units With Two Compressors

To help maximize the life of your compressor(s), there is a start-to-next start delay for each single compressor.

A Minimum ON time and a Minimum Off time may be selected in the Advanced menu (minimum three minutes for single phase compressors). Consult the factory on how to modify the Minimum ON and OFF time settings.

3.1.5Compressor Sequencing

Compressor Sequencing parameter (Service Menu, Options Setup) is intended to maintain equal run times between compressors. This setting has three selection possibilities:

Always use Compressor 1 as lead compressor

Always use Compressor 2 as lead compressor

Auto:

First priority: if the safety timings are acceptable for only one compressor, then it is the next to be started/stopped.

If both compressors are off: the one with fewer working hours is the next to start.

If both compressors are in operation: the one that has been operating longer since the last start is the next to be stopped.

NOTE

The Auto setting attempts to maintain equal run times between compressors.

15

Image 21 Contents
Liebert iCOM Page Table of Contents Installing a Liebert Icom UNIT-TO-UNITNETWORK TeamworkMounting a Large Display on a Wall Figures Tables Large and Small Displays FeaturesESC Icon Key Name Function Keyboard icons and functionsStatus menu, large display, graphical view Accessing Submenus on Small Displays Accessing SubmenusAccessing Submenus on Large Displays Navigating Through the Liebert iCOM MenusMenu tree-Small display, stand-alone or networked Entering a PasswordService Menu Unit Status Menu System View Status Menu Unit 1 View User MenuAdvanced Menu Unit Service Menu Unit # Viewing Multiple Units with a Networked Large DisplayAdvanced Menu Unit # SET User menu icons Service menu icons Unit/Fan Control Start Stop Single Unit FunctionsFan Alarm / Fan Protection Settings Loss of Power AlarmVSD Setpoint VSD Fan Speed Setting AutorestartPump Down High Pressure AlarmDigital Scroll High Temperature Compressor Timing-Units With Two CompressorsCompressor Sequencing Service Offset-Changing System Pressure Settings Motorized Ball Valve in Digital Scroll UnitsMBV Operation After Compressor is Turned Off Temperature proportional band Temperature Proportional BandCompressor Proportional Bands Compressor ControlOne Single-Step Compressor Without Unloaders-One-Step Two Single-Step Compressors Without Unloaders-Two-StepTwo compressors with unloaders four-step Two Compressors With Unloaders-Four-StepDigital scroll capacity modulation, 10-100% variable Digital Scroll CompressorsDifferential Temperatures / Controls Comparator Circuit Temperature Control-Second Cooling SourceDelta T Temperature Difference Between Room and Glycol Chilled Water ControlSecond cooling source and compressorized cooling Reheat configuration types Temperature Control-ReheatGlycool Cooling-Free-Cooling Dual Cooling SourceHeat On ½ Dead Band 100% Off ½ Proportional Band Decreasing TemperatureSCR Reheat Tight ModeStandard Mode Humidity Control Humidification DehumidificationHumidification Humidification Infrared Humidifier Parameters for infrared humidifier controlExternal Humidifier Control-Optional Dehumidification Dehumidification With Comp settingsDehumidification Low Limit Dehumidification Compressor QuantityTemperature and Humidity Control Types Control TypesReheat During Dehumidification Humidity Sensor Reading Control Types Supply Limit-Optional High and Low, Temperature and Humidity EventsCustomer inputs User Inputs / Customer InputsEnable or Disable Time DelayEvent Types and Properties Event TypesMain FAN Overload Event notifications-large or small display Possible Event NotificationsNext Maintenance Calculation Calculation of Next Maintenance and DiagnosticsCalculating Unit Wellness General Maintenance Settings Parameters for Next Maintenance CalculationFans / Heaters / Humidifier Settings and Diagnostics Compressor 1 / 2 Settings and DiagnosticsTeamwork Modes Teamwork ModeApplication of Teamwork Modes No TeamworkTeamwork Mode 1 with two cooling units Standby and Cascade Standby Rotation Typical Standby Lead/Lag FunctionPlacement of Cooling Units U2U Hardware Cables and Network SwitchMinimum Network Switch Requirements Wiring for Unit-to-Unit Communications-U2U Sample Liebert iCOM network configurationsLiebert iCOM U2U Ethernet Network Large Displays Wiring a Liebert iCOM U2U Network Small DisplaysWall-Mount Large Display Combining Large and Small Displays on a U2U NetworkWiring a small display for stand-alone operation Wiring a large display for stand-alone operation Liebert vNSA Ports available for connecting Liebert iCOM control devices298 84mm 305mm 14.25 362mm DPN001136 Rev Location Considerations Necessary Mounting ItemsMounting Instructions Liebert iCOM display dimensions Setpoints parameters Spare Part List-Large Display OnlySpare part list parameters-large display only Event log parametersSensor data Set alarms parametersActive Alarms Active alarms parametersDisplay setup parameters Total run hours parameters Timer parameters-Sleep ModeService contacts parameters Service Menu Parameters Unit diary parameters Unit Diary-Large Display OnlyMaintenance / wellness settings parameters Standby settings / lead-lag parametersWellness COMP2 Wellness HEAT2 Diagnostics / service mode parameters ALM REL 7of Delay Enable Disab Enable Disab Comp 1 Overload Unit X Disconnected WRN Loss of Power LOP MSG, WRN, ALM Call Service MSG, WRN, ALM High Temperature Sensor calibration / setup parameters System / network setup parameters-large display only GBP Network setup parametersStatic RAM Not Available, Invalid, OK HUM Steam Options setup parametersService contact info parameters Service Menu Parameters Service Menu Parameters Page Iti Ne tTi n That