Emerson iCOM user manual Service Menu Parameters

Page 82

Service Menu Parameters

76

Image 82
Contents Liebert iCOM Page Table of Contents Teamwork Installing a Liebert Icom UNIT-TO-UNITNETWORKMounting a Large Display on a Wall Figures Tables Features Large and Small DisplaysESC Keyboard icons and functions Icon Key Name FunctionStatus menu, large display, graphical view Accessing Submenus on Large Displays Accessing SubmenusAccessing Submenus on Small Displays Navigating Through the Liebert iCOM MenusEntering a Password Menu tree-Small display, stand-alone or networkedStatus Menu System View Status Menu Unit 1 View User Menu Service Menu UnitAdvanced Menu Unit Viewing Multiple Units with a Networked Large Display Service Menu Unit #Advanced Menu Unit # SET User menu icons Service menu icons Single Unit Functions Unit/Fan Control Start StopVSD Setpoint VSD Fan Speed Setting Loss of Power AlarmFan Alarm / Fan Protection Settings AutorestartHigh Pressure Alarm Pump DownCompressor Timing-Units With Two Compressors Digital Scroll High TemperatureCompressor Sequencing Motorized Ball Valve in Digital Scroll Units Service Offset-Changing System Pressure SettingsMBV Operation After Compressor is Turned Off Temperature Proportional Band Temperature proportional bandOne Single-Step Compressor Without Unloaders-One-Step Compressor ControlCompressor Proportional Bands Two Single-Step Compressors Without Unloaders-Two-StepTwo Compressors With Unloaders-Four-Step Two compressors with unloaders four-stepDigital Scroll Compressors Digital scroll capacity modulation, 10-100% variableDelta T Temperature Difference Between Room and Glycol Temperature Control-Second Cooling SourceDifferential Temperatures / Controls Comparator Circuit Chilled Water ControlSecond cooling source and compressorized cooling Glycool Cooling-Free-Cooling Temperature Control-ReheatReheat configuration types Dual Cooling SourceOff ½ Proportional Band Decreasing Temperature Heat On ½ Dead Band 100%Tight Mode SCR ReheatStandard Mode Humidification Dehumidification Humidity ControlHumidification Parameters for infrared humidifier control Humidification Infrared HumidifierExternal Humidifier Control-Optional Dehumidification Low Limit Dehumidification With Comp settingsDehumidification Dehumidification Compressor QuantityControl Types Temperature and Humidity Control TypesReheat During Dehumidification Humidity Sensor Reading Control Types High and Low, Temperature and Humidity Events Supply Limit-OptionalUser Inputs / Customer Inputs Customer inputsEvent Types and Properties Time DelayEnable or Disable Event TypesMain FAN Overload Possible Event Notifications Event notifications-large or small displayCalculation of Next Maintenance and Diagnostics Next Maintenance CalculationCalculating Unit Wellness Fans / Heaters / Humidifier Settings and Diagnostics Parameters for Next Maintenance CalculationGeneral Maintenance Settings Compressor 1 / 2 Settings and DiagnosticsApplication of Teamwork Modes Teamwork ModeTeamwork Modes No TeamworkTeamwork Mode 1 with two cooling units Standby Rotation Typical Standby Lead/Lag Function Standby and CascadeU2U Hardware Cables and Network Switch Placement of Cooling UnitsMinimum Network Switch Requirements Sample Liebert iCOM network configurations Wiring for Unit-to-Unit Communications-U2ULiebert iCOM U2U Ethernet Network Wall-Mount Large Display Wiring a Liebert iCOM U2U Network Small DisplaysLarge Displays Combining Large and Small Displays on a U2U NetworkWiring a small display for stand-alone operation Wiring a large display for stand-alone operation Ports available for connecting Liebert iCOM control devices Liebert vNSA298 84mm 305mm 14.25 362mm DPN001136 Rev Necessary Mounting Items Location ConsiderationsMounting Instructions Liebert iCOM display dimensions Spare part list parameters-large display only Spare Part List-Large Display OnlySetpoints parameters Event log parametersSet alarms parameters Sensor dataActive alarms parameters Active AlarmsDisplay setup parameters Timer parameters-Sleep Mode Total run hours parametersService contacts parameters Service Menu Parameters Unit Diary-Large Display Only Unit diary parametersStandby settings / lead-lag parameters Maintenance / wellness settings parametersWellness COMP2 Wellness HEAT2 Diagnostics / service mode parameters ALM REL 7of Delay Enable Disab Enable Disab Comp 1 Overload Unit X Disconnected WRN Loss of Power LOP MSG, WRN, ALM Call Service MSG, WRN, ALM High Temperature Sensor calibration / setup parameters System / network setup parameters-large display only Network setup parameters GBPStatic RAM Not Available, Invalid, OK Options setup parameters HUM SteamService contact info parameters Service Menu Parameters Service Menu Parameters Page Ti n Ne tIti That