| Operation |
| Table 8 | Possible event |
| |||
|
|
|
|
|
| |
|
|
| Internal Delay | Default Delay / Selectable | Type | |
|
| Event | (Before Action Occurs) | (Before Action Occurs) | (default) | |
| MAIN FAN OVERLOAD | 2 seconds | 5 seconds / 0 – 9999 * | ALM | ||
| LOSS OF AIRFLOW | 3 seconds | 3 seconds / 0 – 9999 * | ALM | ||
|
|
|
|
| ||
| CLOGGED FILTERS | 2 seconds | 2 seconds / 0 – 9999 * | WRN | ||
|
|
|
|
| ||
| HIGH ROOM TEMP | 1 Min After Fan On | 30 seconds / 0 – 9999 | Fixed to WRN | ||
|
|
|
|
|
| |
| LOW ROOM TEMP | 1 Min After Fan On | 30 seconds / | 0 – 9999 | Fixed to WRN | |
|
|
|
|
| ||
| HIGH ROOM HUM | 1 Min After Fan On | 30 seconds / 0 – 9999 | Fixed to WRN | ||
|
|
|
|
|
| |
| LOW ROOM HUM | 1 Min After Fan On | 30 seconds / | 0 – 9999 | Fixed to WRN | |
|
|
|
|
| ||
| HIGH TEMP SENSOR A | 1 Min After Fan On | 30 seconds / 0 – 9999 | Fixed to WRN | ||
|
|
|
|
|
| |
| LOW TEMP SENSOR A | 1 Min After Fan On | 30 seconds / | 0 – 9999 | Fixed to WRN | |
|
|
|
|
| ||
| HIGH HUM SENSOR A | 1 Min After Fan On | 30 seconds / 0 – 9999 | Fixed to WRN | ||
|
|
|
|
|
| |
| LOW HUM SENSOR A | 1 Min After Fan On | 30 seconds / | 0 – 9999 | Fixed to WRN | |
|
|
|
|
|
| |
| COMP 1 OVERLOAD | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| COMP 2 OVERLOAD | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| COMP 1 HIGH PRESSURE | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| COMP 2 HIGH PRESSURE | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| COMP 1 LOW PRESSURE | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| COMP 2 LOW PRESSURE | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| COMP 1 PUMPDOWN FAIL | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| COMP 2 PUMPDOWN FAIL | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| DIG SCROLL1 HIGH TEMP | Internal Calc. | no |
| ALM | |
|
|
|
|
|
| |
| DIG SCROLL2 HIGH TEMP | Internal Calc. | no |
| ALM | |
|
|
|
|
| ||
| EL HEAT HIGH TEMP | 5 Sec | 0 sec / 0 – 9999 | WRN | ||
|
|
|
|
| ||
| WORKING HRS EXCEEDED | 0 Sec | 0 sec / 0 – 9999 | Fixed to WRN | ||
|
|
|
|
| ||
| SMOKE DETECTED | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
|
|
|
|
| ||
| WATER UNDER FLOOR | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
|
|
|
|
| ||
| COND | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
|
|
|
|
|
|
|
| LOSS OF FLOW | 5 Sec | 2 sec / 0 – | 9999 * | ALM | |
| Reset Delay: 10 Sec | |||||
|
|
|
|
|
| |
| STBY GLYCOL PUMP ON | 2 Sec | 2 sec / 0 – | 9999 * | ALM | |
| STANDBY UNIT ON | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
| HUMIDIFIER PROBLEM | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
| NO CONNECTION w/Unit1 | Internal Calc. | - |
| WRN | |
| UNIT X DISCONNECTED | Internal Calc. | - |
| WRN | |
| LOSS OF POWER | 0 Sec | No |
| ALM | |
| CUSTOMER INPUT 1 | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
| CUSTOMER INPUT 2 | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
| CUSTOMER INPUT 3 | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
| CUSTOMER INPUT 4 | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
| CALL SERVICE | 2 Sec | 2 sec / 0 – 9999 * | MSG | ||
| HIGH TEMPERATURE | 2 Sec | 2 sec / 0 – 9999 * | MSG | ||
| LOSS OF AIR BLOWER 1 | 2 Sec | 2 sec / 0 – 9999 * | ALM | ||
| REHEAT LOCKOUT | 2 Sec | 2 sec / 0 – 9999 * | WRN | ||
| HUMIDIFIER LOCKOUT | 2 Sec | 2 sec / 0 – 9999 * | WRN | ||
| FC LOCKOUT | 2 Sec | 2 sec / 0 – 9999 * | WRN | ||
| COMPRESSOR(S) LOCKOUT | 2 Sec | 2 sec / 0 – 9999 * | WRN | ||
| COMP 1 SHORT CYCLE | 0 Sec | 0 - 9999 | MSG | ||
| COMP 2 SHORT CYCLE | 0 Sec | 0 - 9999 | MSG |