Emerson iCOM user manual Humidity Control, Humidification Dehumidification

Page 33

Operation

3.6Humidity Control

The control uses the humidity proportional band to determine which operation to perform (dehumidi- fication/humidification) and how intensely to perform it. The Humidity Proportional Band is a user defined range that is divided into two equal parts for dehumidifying and humidifying. The Humidity Setpoint is located between these two equal parts.

An optional Humidity Deadband range can be defined, which is equally divided on either side of the setpoint and separates the two halves of the proportional band. Figure 22 illustrates how the humid- ity proportional band is evenly divided on either side of the humidity setpoint, with and without a deadband.

Figure 22 Humidity proportional band

 

 

Without Deadband

 

- Hum

Humidification

 

Dehumidification

+ Hum

 

 

 

 

 

- 100%

½ Proportional Band

0%

½ Proportional Band

 

 

humidification

 

Setpoint

+ 100%

 

 

 

Dehumidification

 

 

 

 

 

 

With Deadband

 

 

 

Dead-

 

 

 

- Hum

Humidification

band

Dehumidification

+ Hum

 

 

 

 

 

 

 

 

 

- 100%

½ Proportional Band

0%

0%

½ Proportional Band

+ 100%

 

Humidification

Setpoint

Dehumidification

When the return air humidity deviates from the setpoint, it begins to penetrate one of the propor- tional band halves, either dehumidification or humidification. If the return air humidity increases, the control calls for 0% (none) to 100% (full) dehumidifying capacity, based on how far the humidity penetrates the dehumidification portion of the proportional band. If the return air humidity decreases, the control calls for 0% (none) to -100% (full) humidifying capacity based on how far the humidity penetrates the humidification portion of the proportional band.

When the return air humidity reaches the end of the proportional band, either 100% or -100%, full dehumidification or full humidification capacity is provided. No operation is performed when a 0% call is calculated. The control varies the call for dehumidifying and humidifying in 1% increments as the return air humidity moves through the proportional band halves.

The deadband range is used to widen the setpoint. When the return air humidity falls within the deadband, the control operates the same as if the humidity equaled the setpoint exactly. This setting helps maximize component life by preventing excessive component cycling. The Humidity Propor- tional Band and Humidity Deadband parameters are in the Service menu under the Setpoints sub- menu. The Humidity Setpoint parameter is in both the User menu and Service menu under Setpoints.

27

Image 33 Contents
Liebert iCOM Page Table of Contents Installing a Liebert Icom UNIT-TO-UNITNETWORK TeamworkMounting a Large Display on a Wall Figures Tables Large and Small Displays FeaturesESC Icon Key Name Function Keyboard icons and functionsStatus menu, large display, graphical view Accessing Submenus on Small Displays Accessing SubmenusAccessing Submenus on Large Displays Navigating Through the Liebert iCOM MenusMenu tree-Small display, stand-alone or networked Entering a PasswordService Menu Unit Status Menu System View Status Menu Unit 1 View User MenuAdvanced Menu Unit Service Menu Unit # Viewing Multiple Units with a Networked Large DisplayAdvanced Menu Unit # SET User menu icons Service menu icons Unit/Fan Control Start Stop Single Unit FunctionsFan Alarm / Fan Protection Settings Loss of Power AlarmVSD Setpoint VSD Fan Speed Setting AutorestartPump Down High Pressure AlarmDigital Scroll High Temperature Compressor Timing-Units With Two CompressorsCompressor Sequencing Service Offset-Changing System Pressure Settings Motorized Ball Valve in Digital Scroll UnitsMBV Operation After Compressor is Turned Off Temperature proportional band Temperature Proportional BandCompressor Proportional Bands Compressor ControlOne Single-Step Compressor Without Unloaders-One-Step Two Single-Step Compressors Without Unloaders-Two-StepTwo compressors with unloaders four-step Two Compressors With Unloaders-Four-StepDigital scroll capacity modulation, 10-100% variable Digital Scroll CompressorsDifferential Temperatures / Controls Comparator Circuit Temperature Control-Second Cooling SourceDelta T Temperature Difference Between Room and Glycol Chilled Water ControlSecond cooling source and compressorized cooling Reheat configuration types Temperature Control-ReheatGlycool Cooling-Free-Cooling Dual Cooling Source Heat On ½ Dead Band 100% Off ½ Proportional Band Decreasing TemperatureSCR Reheat Tight ModeStandard Mode Humidity Control Humidification DehumidificationHumidification Humidification Infrared Humidifier Parameters for infrared humidifier controlExternal Humidifier Control-Optional Dehumidification Dehumidification With Comp settingsDehumidification Low Limit Dehumidification Compressor QuantityTemperature and Humidity Control Types Control TypesReheat During Dehumidification Humidity Sensor Reading Control Types Supply Limit-Optional High and Low, Temperature and Humidity EventsCustomer inputs User Inputs / Customer InputsEnable or Disable Time DelayEvent Types and Properties Event TypesMain FAN Overload Event notifications-large or small display Possible Event NotificationsNext Maintenance Calculation Calculation of Next Maintenance and DiagnosticsCalculating Unit Wellness General Maintenance Settings Parameters for Next Maintenance CalculationFans / Heaters / Humidifier Settings and Diagnostics Compressor 1 / 2 Settings and DiagnosticsTeamwork Modes Teamwork ModeApplication of Teamwork Modes No TeamworkTeamwork Mode 1 with two cooling units Standby and Cascade Standby Rotation Typical Standby Lead/Lag FunctionPlacement of Cooling Units U2U Hardware Cables and Network SwitchMinimum Network Switch Requirements Wiring for Unit-to-Unit Communications-U2U Sample Liebert iCOM network configurationsLiebert iCOM U2U Ethernet Network Large Displays Wiring a Liebert iCOM U2U Network Small DisplaysWall-Mount Large Display Combining Large and Small Displays on a U2U NetworkWiring a small display for stand-alone operation Wiring a large display for stand-alone operation Liebert vNSA Ports available for connecting Liebert iCOM control devices298 84mm 305mm 14.25 362mm DPN001136 Rev Location Considerations Necessary Mounting ItemsMounting Instructions Liebert iCOM display dimensions Setpoints parameters Spare Part List-Large Display OnlySpare part list parameters-large display only Event log parametersSensor data Set alarms parametersActive Alarms Active alarms parametersDisplay setup parameters Total run hours parameters Timer parameters-Sleep ModeService contacts parameters Service Menu Parameters Unit diary parameters Unit Diary-Large Display OnlyMaintenance / wellness settings parameters Standby settings / lead-lag parametersWellness COMP2 Wellness HEAT2 Diagnostics / service mode parameters ALM REL 7of Delay Enable Disab Enable Disab Comp 1 Overload Unit X Disconnected WRN Loss of Power LOP MSG, WRN, ALM Call Service MSG, WRN, ALM High Temperature Sensor calibration / setup parameters System / network setup parameters-large display only GBP Network setup parametersStatic RAM Not Available, Invalid, OK HUM Steam Options setup parametersService contact info parameters Service Menu Parameters Service Menu Parameters Page Iti Ne tTi n That