Emerson iCOM Humidification Infrared Humidifier, Parameters for infrared humidifier control

Page 34

Operation

3.6.1Humidification Infrared Humidifier

There are two types of infrared humidifiers: small pan (IFS) and large pan (IFL). The operating mode of each is similar, however, some of the variables or timings differ.

Infrared humidifiers are started at 100% humidification request, and stopped at 0%. Infrared humid- ifiers cannot be driven in proportional mode.

Table 5 Parameters for infrared humidifier control

Parameter

IFS Default

IFL Default

 

 

 

Humidity in Last xx Hours

15 hours

15 hours

 

 

 

Prefill Time

30 seconds

60 seconds

 

 

 

Fill Time

4 minutes

7 minutes

 

 

 

Humidifier On Time

8 or 10 minutes

10 minutes

 

 

 

Flush Rate

150%

150%

 

 

 

An autoflush system automatically controls a water makeup valve to maintain proper levels in the infrared humidifier water pan during humidifier operation. If humidification is needed and 15 hours have elapsed since the last time the humidifier was on, then the humidifier is not turned on until the valve completes an initial fill of the humidifier pan. This pre-fill is about 30 seconds for a small pan and 60 seconds for a large pan. The valve continues to fill and flush the pan for about 4-1/2 minutes for a small pan or 7-1/2 minutes for a large pan. Pan size is selected based on unit specifications and is preset at the factory.

During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri- odically to add water to the pan (about 45 seconds every 7 minutes of humidifier operation for a small pan, or 80 seconds every 10 minutes of operation for a large pan). This adds enough water to the pan to cause about a third of the total water used to be flushed out of the overflow standpipe located in the humidifier pan. This action helps to remove solids from the pan. The flush rate is adjustable from 110% to 500% in 10% intervals. Default is 150%. If the water quality is poor, it may be desirable to increase the water flushing action above the normal 150% rate. Also, if the supply water pressure is low, the flush rate adjustment can be increased so that sufficient water level is maintained during humidification. The flush rate parameter, Infrared Flush Rate (Service Menu, Options Setup), is adjustable from 110%-500%.

External Humidifier Control—Optional

A factory-supplied option may be provided to allow a start-stop command to be sent to the control of a remote-mounted humidifier.

28

Image 34
Contents Liebert iCOM Page Table of Contents Teamwork Installing a Liebert Icom UNIT-TO-UNITNETWORKMounting a Large Display on a Wall Figures Tables Features Large and Small DisplaysESC Keyboard icons and functions Icon Key Name FunctionStatus menu, large display, graphical view Accessing Submenus on Large Displays Accessing SubmenusAccessing Submenus on Small Displays Navigating Through the Liebert iCOM MenusEntering a Password Menu tree-Small display, stand-alone or networkedStatus Menu System View Status Menu Unit 1 View User Menu Service Menu UnitAdvanced Menu Unit Viewing Multiple Units with a Networked Large Display Service Menu Unit #Advanced Menu Unit # SET User menu icons Service menu icons Single Unit Functions Unit/Fan Control Start StopVSD Setpoint VSD Fan Speed Setting Loss of Power AlarmFan Alarm / Fan Protection Settings AutorestartHigh Pressure Alarm Pump DownCompressor Timing-Units With Two Compressors Digital Scroll High TemperatureCompressor Sequencing Motorized Ball Valve in Digital Scroll Units Service Offset-Changing System Pressure SettingsMBV Operation After Compressor is Turned Off Temperature Proportional Band Temperature proportional bandOne Single-Step Compressor Without Unloaders-One-Step Compressor ControlCompressor Proportional Bands Two Single-Step Compressors Without Unloaders-Two-StepTwo Compressors With Unloaders-Four-Step Two compressors with unloaders four-stepDigital Scroll Compressors Digital scroll capacity modulation, 10-100% variableDelta T Temperature Difference Between Room and Glycol Temperature Control-Second Cooling SourceDifferential Temperatures / Controls Comparator Circuit Chilled Water ControlSecond cooling source and compressorized cooling Glycool Cooling-Free-Cooling Temperature Control-ReheatReheat configuration types Dual Cooling SourceOff ½ Proportional Band Decreasing Temperature Heat On ½ Dead Band 100%Tight Mode SCR ReheatStandard Mode Humidification Dehumidification Humidity ControlHumidification Parameters for infrared humidifier control Humidification Infrared HumidifierExternal Humidifier Control-Optional Dehumidification Low Limit Dehumidification With Comp settingsDehumidification Dehumidification Compressor QuantityControl Types Temperature and Humidity Control TypesReheat During Dehumidification Humidity Sensor Reading Control Types High and Low, Temperature and Humidity Events Supply Limit-OptionalUser Inputs / Customer Inputs Customer inputsEvent Types and Properties Time DelayEnable or Disable Event TypesMain FAN Overload Possible Event Notifications Event notifications-large or small displayCalculation of Next Maintenance and Diagnostics Next Maintenance CalculationCalculating Unit Wellness Fans / Heaters / Humidifier Settings and Diagnostics Parameters for Next Maintenance CalculationGeneral Maintenance Settings Compressor 1 / 2 Settings and DiagnosticsApplication of Teamwork Modes Teamwork ModeTeamwork Modes No TeamworkTeamwork Mode 1 with two cooling units Standby Rotation Typical Standby Lead/Lag Function Standby and CascadeU2U Hardware Cables and Network Switch Placement of Cooling UnitsMinimum Network Switch Requirements Sample Liebert iCOM network configurations Wiring for Unit-to-Unit Communications-U2ULiebert iCOM U2U Ethernet Network Wall-Mount Large Display Wiring a Liebert iCOM U2U Network Small DisplaysLarge Displays Combining Large and Small Displays on a U2U NetworkWiring a small display for stand-alone operation Wiring a large display for stand-alone operation Ports available for connecting Liebert iCOM control devices Liebert vNSA298 84mm 305mm 14.25 362mm DPN001136 Rev Necessary Mounting Items Location ConsiderationsMounting Instructions Liebert iCOM display dimensions Spare part list parameters-large display only Spare Part List-Large Display OnlySetpoints parameters Event log parametersSet alarms parameters Sensor dataActive alarms parameters Active AlarmsDisplay setup parameters Timer parameters-Sleep Mode Total run hours parametersService contacts parameters Service Menu Parameters Unit Diary-Large Display Only Unit diary parametersStandby settings / lead-lag parameters Maintenance / wellness settings parametersWellness COMP2 Wellness HEAT2 Diagnostics / service mode parameters ALM REL 7of Delay Enable Disab Enable Disab Comp 1 Overload Unit X Disconnected WRN Loss of Power LOP MSG, WRN, ALM Call Service MSG, WRN, ALM High Temperature Sensor calibration / setup parameters System / network setup parameters-large display only Network setup parameters GBPStatic RAM Not Available, Invalid, OK Options setup parameters HUM SteamService contact info parameters Service Menu Parameters Service Menu Parameters Page Ti n Ne tIti That