Operation
GLYCOOL™ Cooling—Free-Cooling
When GLYCOOL cooling is available, the temperature control will calculate a total cooling require- ment of 200% rather than 100%. Assuming that full GLYCOOL capacity is available, the GLYCOOL valve opens proportionally as the requirement for cooling rises from 0 to 100%. If more than 100% cooling is required, then the compressors are activated at 150% and 200% respectively (133%, 163%, 180% and 200% for a
For example, if the GLYCOOL capacity is 60%, then the GLYCOOL valve would be full open at 60% cooling requirement and the compressors would activate at 110% and 160% cooling requirement. In order to reduce compressor cycling and prevent hunting, GLYCOOL capacity first becomes available when the entering glycol temperature is at least 8°F (4.4°C) (22% capacity) below the return air tem- perature, or 3°F (1.7°C) below the return air temperature for two hours. GLYCOOL capacity is 100% when the glycol temperature is 25°F (13.9°C) below the return air temperature. The system will con- tinue to operate in
Dual Cooling Source
If dual cooling is available, the sensible cooling system operates in the same manner as a GLYCOOL system, except that it is assumed that 100% chilled water capacity is available any time the chilled water temperature is 3°F (1.7°C) below the return air temperature.
3.5Temperature Control—Reheat
If the room air temperature becomes too cold, the control will call for heating. Heating mode is con- trolled by the Temperature Proportional Band, explained in 3.3.1 - Temperature Proportional Band.
3.5.1Three-Stage Electric, Hot Gas and Hot Water Reheat
The Reheat Proportional Band is divided into three equal parts, each representing one reheat stage. As the Temperature Proportional Band increases the call for heating from 0% to
Table 4 Reheat configuration types
Type | A | B | C | D | E | F | G | H | I |
|
|
|
|
|
|
|
|
|
|
Stage 1 | Electric 1 | Electric 1 | Electric 1 | Hot Gas | Hot Gas | Hot Gas | Hot Water | Hot Water | Hot Water |
|
|
|
|
|
|
|
|
|
|
Stage 2 | - | Electric 2 | Electric 2 | - | Electric 1 | Electric 1 | - | Electric 1 | Electric 1 |
|
|
|
|
|
|
|
|
|
|
Stage 3 | - | - | Electric 3 | - | - | Electric 2 | - | - | Electric 2 |
|
|
|
|
|
|
|
|
|
|
NOTE
1. Hot gas / hot water are not influenced by the setting of electric reheat during dehumidification.
2. Hot gas output will be set only if the selected compressor is in operation.
23