Operation
Digital Scroll Compressors
A compressor with a suction cutoff unloader can only modulate its capacity between two distinct lev- els: fully loaded and half loaded. A digital scroll compressor can modulate its capacity anywhere between
Digital scroll capacity modulation is achieved by energizing and
Figure 15 Digital scroll capacity modulation, 10-100% variable
Call for Cooling: 66% 100% Loaded
Solenoid
0% Loaded
Solenoid Energized
Solenoid
Solenoid Energized
0 | 5 | 10 | 15 | 20 | 25 | 30 | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| ||||
|
| Modulation Cycle |
|
| Modulation Cycle |
|
| ||
|
|
|
|
|
|
|
|
|
|
On single and dual digital scroll compressor systems, the first compressor is started at 25% calculated output from the temperature proportional band and stopped at 10%. On dual digital scroll compressor systems, the second compressor is started at 35% and stopped at 20%, see Figure 16. When a com- pressor is started, the solenoid is energized longer than it is
Figure 16 Single and dual digital scroll compressor activation points
Temp Setpoint: 70°F |
|
|
| Comp 1 & 2 On | |
|
|
| Fully Loaded | ||
Proportional Band : 8°F |
| Comp 2 On Partially | |||
|
| ||||
Deadband : 2°F |
| Loaded |
|
| |
| Comp 1 On Partially |
|
| ||
½ Dead- | Loaded |
|
| ||
|
|
|
| ||
band |
|
|
|
|
|
70 | 71 | 72 | 73 | 74 | 75 |
0% | Comp 1 |
|
|
| + 100% |
|
|
| Cooling | ||
Cooling | Off |
|
|
| |
|
|
|
|
Comp 2
Off
½ Proportional Band
Increasing Temperature
20