7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary.

Fault Code

System Failure

 

Recommended Troubleshooting

 

 

 

 

Fault 1

No card is plugged into the

1.

Make sure the purge card is seated properly.

*No Purge Card*

purge card slot.

2.

Inspect the purge card and connector on the relay module for

 

 

 

damage or contaminants.

 

 

3.

Reset and sequence the relay module.

 

 

4.

If the fault code reappears, replace the purge card.

 

 

5.

Reset and sequence the relay module.

 

 

6.

If the fault persists, replace the relay module.

 

 

 

 

Fault 2

Excess noise or device

1.

Check the relay module and display module connections.

*AC Frequen/Noise*

running on slow ac.

2.

Reset and sequence the relay module.

Fault 3

Ac line dropout detected.

3.

Check the relay module power supply and make sure that both

*AC Line Dropout*

 

 

frequency and voltage meet the specifications.

 

 

 

 

Fault 4

Device running on fast ac.

4.

Check the backup power supply, as appropriate.

*AC Frequency*

 

 

 

 

 

 

 

Fault 5

Low ac line detected.

 

 

*Low Line Voltage*

 

 

 

 

 

 

 

Fault 6

Purge card timing changed

1.

Make sure the purge card is seated properly.

*Purge Card Error*

since card was initially read.

2.

Inspect the purge card and connector on the relay module for

 

 

 

damage or contaminants.

 

 

3.

Reset and sequence the relay module.

 

 

4.

If the fault code reappears, replace the purge card.

 

 

5.

Reset and sequence the relay module.

 

 

6.

If the fault persists, replace the relay module.

 

 

 

 

Fault 7

Flame sensed when flame

1.

Check wiring and correct any errors. Make sure that flame

*Flame Amplifier*

not present.

 

sensor wires are in separate conduits. Check for noise

 

 

 

coupling into the flame detector leadwires.

 

 

2.

Make sure that flame detector and flame amplifier are

 

 

 

compatible.

 

 

3.

Remove the flame amplifier and inspect connections. Reseat

 

 

 

the amplifier.

 

 

4.

Reset and sequence the relay module.

 

 

5.

If the code reappears, replace the amplifier and/or the flame

 

 

 

detector.

Fault 8

Flame sensed when no

6.

If the fault persists, replace the relay module.

*Flame Amp/Shutr*

signal expected during

 

 

 

shutter-check or Ampli-

 

 

 

Check™ versions.

 

 

 

 

 

 

Fault 9

Flame sensed when shutter

1.

Check that flame is not present in the combustion chamber;

*Flame Detected*

open and no flame is

 

correct any errors.

 

expected during STANDBY.

2. Check wiring and correct any errors. Make sure that flame

 

 

 

sensor wires are in separate conduits. Check for noise

 

 

 

coupling into flame detector leadwires.

 

 

3.

Remove the flame amplifier and inspect its connections.

 

 

 

Reseat the amplifier.

 

 

4.

Reset and sequence the relay module.

 

 

5.

If the code reappears, replace the amplifier and/or the flame

 

 

 

detector.

 

 

6.

If the fault persists, replace the relay module.

 

 

 

 

Fault 10

Preignition Interlock fault

1.

Check wiring and correct any errors.

*Preignition ILK*

during STANDBY

2.

Check Preignition Interlock switches to assure proper

 

*EC/RM7800, 7840, 7838B

 

functioning.

 

only).

3.

Check fuel valve operation.

 

 

4.

Reset and sequence the relay module; monitor the Preignition

 

 

 

Interlock status.

 

 

5.

If the code persists, replace the relay module.

 

 

 

 

(continued)

65-0229—1

10

Image 10
Contents Checkout Summary System CheckoutEquipment Recommended Explosion Hazard Can cause serious injury or deathPreliminary Inspection Flame Signal MeasurementInitial Lightoff Checks Proved Pilot SystemsDirect Spark Ignition Systems Pilot Turndown Test ALL Installations Using a Pilot Ignition Interference Test ALL Flame Rods To Eliminate Ignition InterferenceFlame Signal With Hot Combustion Chamber All Installations Ignition Spark Response Test ALL Ultraviolet DetectorsTroubleshooting System DiagnosticsKeyboard Display Module Sequence and Status Hold Messages Main IGN mmss Pilot IGN mmssPostpurge mmss Running on slow ac Reset and sequence the relay module Fault Code System Failure Recommended Troubleshooting Hold and Fault Message SummaryPrepurge Inspect the fan make sure there is no blockage of the air Prepurge RM7838A Explosion Hazard Can cause explosion, serious injury or deathThis fault indicates Remove power to the device Flame amplifier Unused faults Relay Module self-test Reset and sequence the relay module Series Relay Modules Home and Building Control