7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).

Fault Code

System Failure

 

Recommended Troubleshooting

 

 

 

 

Fault 51

Flame signal value is too high

1.

Make sure that flame detector and flame amplifier are

*Flame Too Strong*

to be valid.

 

compatible.

 

 

2.

Remove the flame amplifier and inspect the connections. Reset

 

 

 

the flame amplifier.

 

 

3.

Reset and sequence the relay module.

 

 

4.

Check the flame detector sighting position, reset and cycle.

 

 

5.

Verify that no ignition noise is present in the F lead due to wire

 

 

 

routing.

 

 

6.

Measure the flame strength. Verify it meets specifications. If

 

 

 

not, refer to the flame amplifier and/or flame detector checkout

 

 

 

procedures.

 

 

7.

If the code reappears, replace the flame amplifier and/or the

 

 

 

flame detector.

 

 

8.

If the fault persists, replace the relay module.

 

 

 

 

Fault 52

Pilot Valve 2 (terminal 21) was

1.

Inspect terminal 21 and connections. Make sure that the valve

*Call Service*

off when it should be on.

 

is operating properly.

 

 

2.

Reset and sequence the relay module.

 

 

3.

If the fault persists, replace the relay module.

 

 

 

 

Fault 53

Lockout Input fault

1.

Check wiring; correct any errors.

*Lockout Switch*

(EC/RM7810, 7820, 7830,

2.

Inspect the Lockout Switch to make sure it is working

 

7850 only).

 

properly.

 

 

3.

Reset and sequence the relay module. During STANDBY or

 

 

 

PREPURGE, measure the voltage between terminal 20 and G

 

 

 

(ground). Supply voltage should be present. If not, the

 

 

 

lockout switch is defective and needs replacing.

 

 

4.

If the fault persists, replace the relay module.

 

 

 

 

Fault 54

Combustion pressure switch

1.

Check wiring; correct any errors.

*Comb. Pressure*

fault (Fulton pulse only).

2.

Inspect the Combustion Pressure Switch to make sure it is

 

 

 

working correctly.

 

 

3.

Reset and sequence the relay module.

 

 

4.

During STANDBY or PREPURGE, measure the voltage

 

 

 

between terminal 20 and G (ground). Supply voltage should

 

 

 

be present. If not, the Combustion Pressure Switch is

 

 

 

defective and needs replacing.

 

 

5.

If the fault persists, replace the relay module.

 

 

 

 

Fault 55

Purge fan switch is on when it

1.

Check wiring; correct any errors.

*Purge Fan Sw. On*

should be off (Fulton pulse

2.

Inspect the Purge Fan Switch terminal 18 and its connections.

 

only).

 

Make sure the switch is working correctly and is not jumpered

 

 

 

or welded.

 

 

3.

Reset and sequence the relay module.

 

 

4.

If the fault persists, replace the relay module.

 

 

 

 

Fault 56

Block intake fault

1.

Check wiring; correct any errors.

*Block Intake*

(Fulton pulse only).

2.

Inspect the Block Intake Switch and make sure it is working

 

 

 

properly.

 

 

3.

Reset and sequence the relay module.

 

 

4.

During PREPURGE, measure the voltage between terminal 7

 

 

 

and G (ground). Supply voltage should be present. If not, the

 

 

 

Block Intake Switch is defective and needs replacing.

 

 

5.

If the fault persists, replace the relay module.

 

 

 

 

Fault 57

Purge Fan Switch is off when

1.

Inspect the Prepurge Fan Switch terminal 18 and the

*Purge Fan Sw. Off*

it should be on (Fulton pulse

 

connections. Make sure the switch is working properly.

 

only).

2.

Reset and sequence the relay module.

 

 

3.

If the fault persists, replace the relay module.

 

 

 

 

Faults 58 - 66

Unused faults

 

*Call Service*

 

 

 

 

 

 

 

Fault 67

L1 and L2

1.

Check L1 and L2 for proper line phasing.

*AC Phase*

miswired/exchanged

 

 

 

(EC/RM7810, 7820, 7830,

 

 

 

7850 only).

 

 

 

 

 

 

 

 

 

(continued)

65-0229—1

16

Image 16
Contents System Checkout Equipment RecommendedCheckout Summary Explosion Hazard Can cause serious injury or deathFlame Signal Measurement Initial Lightoff ChecksPreliminary Inspection Proved Pilot SystemsDirect Spark Ignition Systems Pilot Turndown Test ALL Installations Using a Pilot Ignition Interference Test ALL Flame Rods To Eliminate Ignition InterferenceFlame Signal With Hot Combustion Chamber All Installations Ignition Spark Response Test ALL Ultraviolet DetectorsTroubleshooting System DiagnosticsKeyboard Display Module Sequence and Status Hold Messages Main IGN mmss Pilot IGN mmssPostpurge mmss Running on slow ac Reset and sequence the relay module Fault Code System Failure Recommended Troubleshooting Hold and Fault Message SummaryPrepurge Inspect the fan make sure there is no blockage of the air Prepurge RM7838A Explosion Hazard Can cause explosion, serious injury or deathThis fault indicates Remove power to the device Flame amplifier Unused faults Relay Module self-test Reset and sequence the relay module Series Relay Modules Home and Building Control