2nd Ave 7800 Series Flame Signal With Hot Combustion Chamber All Installations

Page 6

7800 SERIES RELAY MODULES

IGNITION SPARK RESPONSE TEST (ALL ULTRAVIOLET DETECTORS)

Test to make certain that the ignition spark is not actuating the FLAME LED:

1.Close the pilot and main burner manual fuel shut-off valve(s).

2.Start the burner and use the Run/Test Switch (if available) to stop the sequence in the PILOT IGN period. Ignition spark should occur, but the flame signal should not be more than 0.5 Vdc.

3.If the flame signal is higher than 0.5 Vdc and the FLAME LED does come on, consult the equipment operating manual and resight the detector farther out from the spark, or away from possible reflection. It may be necessary to construct a barrier to block the ignition spark from the detector view. Continue adjustments until the flame signal due to ignition spark is less than 0.5 Vdc.

NOTE: The Honeywell Q624A and Q652A,B Solid State Spark Generators prevent detection of ignition spark when properly applied with C7027, C7035, C7044 or C7061 Ultraviolet Flame Detectors. The Q624A and Q652B are only for use with gas pilots; the Q652A is only for oil applications.

Response To Other Ultraviolet Sources

Some sources of artificial light (such as incandescent or fluorescent bulbs, mercury sodium vapor lamps and daylight) produce small amounts of ultraviolet radiation. Under certain conditions, an ultraviolet detector responds to these sources as if it is sensing a flame. To check for proper detector operation, check the Flame Failure Response Time (FFRT) and conduct Safety Shutdown Tests under all operating conditions.

Flame Signal With Hot Combustion Chamber (All Installations)

1.With all initial start-up tests and burner adjustments completed, operate the burner until the combustion chamber is at the maximum expected temperature.

2.Observe the equipment manufacturer warm-up instructions.

3.Recycle the burner under these hot conditions and measure the flame signal. Check the pilot alone, the main burner flame alone, and both together (unless monitoring only the pilot flame when using an intermittent pilot, or only the main burner flame when using DSI). Check the signal at both High and Low Firing Rate positions and while modulating, if applicable.

4.Check the FFRT of the flame amplifier and relay module.

5.Lower the setpoint of the operating controller and observe the time it takes for the burner flame to go out. This should be within the maximum FFRT.

6.If the flame signal is too low or unsteady, check the flame detector temperature. Relocate the detector if the temperature is too high.

7.If necessary, realign the sighting to obtain the proper signal and response time.

8.If the response time is still too slow, replace the Plug-in Flame Signal Amplifier.

9.If the detector is relocated or resighted, or the amplifier is replaced, repeat all required Checkout tests.

SAFETY SHUTDOWN TESTS (ALL INSTALLATIONS)

Perform these tests at the end of Checkout, after all other tests are completed. If used, the external alarm should turn on. Press the RESET pushbutton on the relay module to restart the system.

1.Opening a Preignition Interlock during the STANDBY or PREPURGE period (only for RM7800, EC/RM7840, RM7838B, EC7810, EC7820, EC/RM7830, EC/ RM7850).

a.*Preignition ILK* fault is displayed on the Keyboard Display Module. Fault code 10 or 33 is displayed to denote the fault.

b.Safety shutdown occurs.

2.Opening a Lockout Interlock during PREPURGE, PILOT IGN, MAIN IGN or RUN period (only for RM7800, EC/RM7840, RM7838B, EC7810, EC7820, EC/RM7830, EC/RM7850).

a.*Lockout ILK* fault is displayed on the Keyboard Display Module. Fault code 11 or 12 or 21 or 29 is displayed to denote the fault.

b.Safety shutdown occurs.

3.Detection of flame 40 seconds after entry to STANDBY from RUN, fault code 9. Detection of flame from ten seconds up to 30 seconds into PREPURGE time.

a.Simulate a flame to cause the flame signal voltage level to be at least 1.25 Vdc for 40 seconds after entry to STANDBY from RUN and also simulate a flame signal for 10 seconds to 30 seconds for PREPURGE.

b.*Flame Detected* fault is displayed on the Keyboard Display Module. Fault code 9 or 15 or 18 is displayed to denote the fault.

c.Safety shutdown occurs.

4.Failure to ignite pilot.

a.Close pilot and main fuel manual shutoff valve(s).

b.Cycle burner on.

c.Automatic pilot valve(s) should be energized but the pilot cannot ignite.

d.*Pilot Flame Fail* fault is displayed on the Keyboard Display Module. Fault code 28 is displayed four or ten seconds, depending on the jumper configuration selection for Pilot Flame Establishing Period (PFEP) after the pilot valve(s) is energized to denote the fault.

e.Safety shutdown occurs.

5.Failure to ignite main (only interrupted pilot application).

a.Open the manual pilot valve(s); leave the main fuel manual shutoff valve(s) closed.

b.Depress the RESET button.

c.Start the system.

d.The pilot should ignite and the flame signal should be at least 1.25 Vdc but the main burner cannot light.

e.The flame signal should drop below 1.25 Vdc within the FFRT of the amplifier and the relay module after the interrupted pilot goes out.

f.*Main Flame Ign.* fault is displayed on the Keyboard Display Module. Fault code 19 is displayed to denote the fault.

g.Safety shutdown occurs.

65-0229—1

6

Image 6
Contents Checkout Summary System CheckoutEquipment Recommended Explosion Hazard Can cause serious injury or deathPreliminary Inspection Flame Signal MeasurementInitial Lightoff Checks Proved Pilot SystemsDirect Spark Ignition Systems Pilot Turndown Test ALL Installations Using a Pilot Ignition Interference Test ALL Flame Rods To Eliminate Ignition InterferenceFlame Signal With Hot Combustion Chamber All Installations Ignition Spark Response Test ALL Ultraviolet DetectorsTroubleshooting System DiagnosticsKeyboard Display Module Sequence and Status Hold Messages Pilot IGN mmss Main IGN mmssPostpurge mmss Running on slow ac Reset and sequence the relay module Hold and Fault Message Summary Fault Code System Failure Recommended TroubleshootingPrepurge Inspect the fan make sure there is no blockage of the air Prepurge RM7838A Explosion Hazard Can cause explosion, serious injury or deathThis fault indicates Remove power to the device Flame amplifier Unused faults Relay Module self-test Reset and sequence the relay module Series Relay Modules Home and Building Control