2nd Ave 7800 Series installation instructions Prepurge RM7838A

Page 13

 

 

 

7800 SERIES RELAY MODULES

 

 

 

 

 

 

Table 3. Hold and Fault Message Summary (continued).

 

 

 

 

 

 

 

Fault Code

System Failure

 

Recommended Troubleshooting

 

 

 

 

 

 

 

Fault 27

Start Switch was on during

1.

Start Switch held on too long.

 

 

*Start Switch On*

PREPURGE (RM7838A,

2.

Check wiring; verify that Start Switch is correctly connected.

 

 

RM7838B only).

3.

Make sure that the Start Switch is functioning properly and that

 

 

 

 

the switch contacts are free of contaminants.

 

 

 

4.

Reset and sequence the relay module to PREPURGE; set the

 

 

 

 

Run/Test Switch to Test. Make sure there is no power at

 

 

 

 

terminal 6 during PREPURGE.

 

 

 

 

5.

If steps 1 through 3 are correct and the fault persists, replace

 

 

 

 

the relay module.

 

 

 

 

 

 

 

Fault 28

Pilot flame failure.

1.

Check pilot valve wiring and operation. Correct any errors.

 

*Pilot Flame Fail*

 

2.

Check fuel supply.

 

 

 

 

3.

Check pilot pressure and repeat pilot turndown test.

 

 

 

4.

Check ignition transformer electrode, flame detector, flame

 

 

 

 

detector sighting and flame amplifier.

 

 

 

 

5.

If steps 1 through 4 are correct and the fault persists, replace

 

 

 

 

the relay module.

 

 

 

 

 

 

 

 

Fault 29

Lockout Interlock fault.

1.

Check wiring; correct any errors.

 

 

*Lockout ILK*

 

2.

Inspect the fan; make sure that there is no blockage of the air

 

 

 

 

intake and that it is supplying air.

 

 

 

 

3.

Make sure that the Lockout Interlock Switches are working

 

 

 

 

properly and that all switch contacts are free of contaminants.

 

 

 

4.

Reset and sequence the relay module to PREPURGE (place the

 

 

 

 

Run/Test Switch in the Test position, if available). Measure the

 

 

 

 

voltage between terminals 7 and G (ground). Line voltage

 

 

 

 

should be present.

 

 

 

 

5.

If steps 1 through 4 are correct and the fault persists, replace

 

 

 

 

the relay module.

 

 

 

 

 

 

 

Fault 30

Running Interlock fault.

1.

Inspect the Running Interlocks, including the Airflow Switch,

 

*Running ILK*

 

 

and the connections.

(continued)

 

 

 

 

 

 

 

2.

Make sure that the Running Interlocks, including the Airflow

 

 

 

 

Switch, are functioning properly and that switch contacts are

 

 

 

 

free of contaminants.

 

 

 

 

3.

Reset and sequence the relay module to PREPURGE. Set the

 

 

 

 

Run/Test Switch, if available, to Test. Measure the voltage

 

 

 

 

between terminal 7 and G (ground). Line voltage should be

 

 

 

 

present.

 

 

 

 

4.

If steps 1 through 3 are correct and the fault persists, replace

 

 

 

 

the relay module.

 

 

 

 

 

 

 

 

Fault 31

Low Fire Interlock Switch

1.

Check wiring; correct any errors.

 

 

*Low Fire Sw. Off*

failure to close during RUN

2.

Reset and sequence the relay module.

 

 

 

(RM7838B only).

3.

Use either the manual motor position to drive the motor to the

 

 

 

 

Low Fire position, or use the Run/Test Switch option, if

 

 

 

 

available. Sequence to Run drive to Low Fire and place in the

 

 

 

 

Test position. Adjust the Low Fire Switch while in this state to

 

 

 

 

make sure it is closing properly.

 

 

 

 

4.

While in Run, drive to Low Fire state, measure the voltage

 

 

 

 

between terminal 18 and G (ground). Line voltage should be

 

 

 

 

present. If not, the switch adjustment is incorrect and/or the

 

 

 

 

switch is defective and needs replacement.

 

 

 

5.

Reset and sequence the relay module. If line voltage was

 

 

 

 

present between the Low Fire Switch and terminal 18 and the

 

 

 

 

fault persists, replace the relay module.

 

 

 

 

 

 

 

 

 

 

 

 

(continued)

13

65-0229—1

Image 13
Contents Equipment Recommended System CheckoutCheckout Summary Explosion Hazard Can cause serious injury or deathInitial Lightoff Checks Flame Signal MeasurementPreliminary Inspection Proved Pilot SystemsDirect Spark Ignition Systems Pilot Turndown Test ALL Installations Using a Pilot To Eliminate Ignition Interference Ignition Interference Test ALL Flame RodsIgnition Spark Response Test ALL Ultraviolet Detectors Flame Signal With Hot Combustion Chamber All InstallationsSystem Diagnostics TroubleshootingKeyboard Display Module Sequence and Status Hold Messages Main IGN mmss Pilot IGN mmssPostpurge mmss Running on slow ac Reset and sequence the relay module Fault Code System Failure Recommended Troubleshooting Hold and Fault Message SummaryPrepurge Inspect the fan make sure there is no blockage of the air Prepurge RM7838A Can cause explosion, serious injury or death Explosion HazardThis fault indicates Remove power to the device Flame amplifier Unused faults Relay Module self-test Reset and sequence the relay module Series Relay Modules Home and Building Control