| 7800 SERIES RELAY MODULES | |
|
|
|
| |
| Table 3. Hold and Fault Message Summary (continued). | |||
|
|
|
| |
Fault Code | System Failure |
| Recommended Troubleshooting | |
|
|
|
| |
Fault 45 | Low Fire Interlock switch failure | 1. | Check wiring; correct any errors. | |
*Low Fire Sw. Off* | to close or stay closed. | 2. | Reset and sequence the relay module. | |
|
| 3. | Use either the manual motor position to drive the motor to | |
|
|
| the Low Fire position, or use the Run/Test Switch option, if | |
|
|
| available. Sequence to Run, drive to Low Fire and place in | |
|
|
| the Test position. Adjust the Low Fire Switch while in this | |
|
|
| state to make sure it is closing properly. | |
|
| 4. | While in Run, drive to Low Fire state, measure the voltage | |
|
|
| between terminal 18 and G (ground). Line voltage should | |
|
|
| be present. If not, the switch adjustment is incorrect | |
|
|
| and/or the switch is defective and needs replacement. | |
|
| 5. | If steps 1 through 4 are correct and the fault still persists, | |
|
|
| replace the relay module. | |
|
|
|
| |
Fault 46 | This fault indicates: | 1. | Remove power to the device. | |
*Flame Amp Type* | a. The Flame Failure Response | 2. | Reseat the flame amplifier and reset and sequence the relay | |
| Time (FFRT) or TYPE input |
| module. | |
| from the amplifier changed | 3. | For EC/RM7890 only; make sure that Jumper JR2 is | |
| while the device was |
| completely clipped if a | |
| powered; or |
| being used. If Jumper JR2 is intact (relight option is | |
| b. A standard amplifier was |
| selected), use 0.8 second FFRT amplifier. | |
| used in a pilot valve | 4. | For RM7838B only; make sure that a Shutter Check Flame | |
| application; or |
| Amplifier is being used with the Pilot Valve Hold option | |
| c. A |
| selected. | |
| Amplifier was used with the |
|
|
|
| relight option on the |
|
|
|
| RM7890 Relay Module. |
|
|
|
|
|
|
| |
Fault 47 | The configuration jumpers differ | 1. | Inspect the jumper connections. Make sure that clipped | |
*Jumpers Changed* | from the sample taken at startup. |
| jumpers are completely removed. | |
|
| 2. | Reset and sequence the relay module. | |
|
| 3. | If fault persists, replace the relay module. | |
|
|
|
|
|
Fault 48 | V2S valve terminal, used as a |
| WARNING | |
*Delayed MV On* | delayed main valve, was on when |
| ||
| it should be off. |
| Explosion Hazard. | |
|
|
| Can cause explosion, serious injury or death. | |
|
|
| 1. Remove system power, turn off fuel supply. | |
|
|
| 2. Check wiring; correct any errors. | |
|
|
| 3. Inspect the V2S Fuel Valve and its connections. | |
|
|
| Make sure the switch is working correctly and is not | |
|
|
| jumpered or welded. | |
|
|
| 4. Reset and sequence the relay module. | |
|
|
| 5. If fault persists, replace the relay module. | |
|
|
|
|
|
Fault 49 | The manual open switch was on |
| WARNING | |
when it should be off. |
| |||
|
|
| Explosion Hazard. | |
|
|
| Can cause explosion, serious injury or death. | |
|
|
| 1. Remove system power, turn off fuel supply. | |
|
|
| 2. Check wiring; correct any errors. | |
|
|
| 3. Inspect the | |
|
|
| connections. Make sure the switch is working | |
|
|
| correctly and is not jumpered or welded. | |
|
|
| 4. Reset and sequence the relay module. | |
|
|
| 5. If fault persists, replace the relay module. | |
|
|
|
| |
Fault 50 | The sequence logic detected a | 1. | Inspect the jumpers and refer to the installation instructions | |
*Jumpers Wrong* | combination of jumpers that is |
| for compatible jumper configurations. | |
| illegal for the sequence eg, if it is | 2. | Make sure that clipped jumpers are completely removed. | |
| correct to clip Jumper JR1 or | 3. | Reset and sequence the relay module. | |
| Jumper JR2, but not both, this | 4. | If fault persists, replace the relay module. | |
| fault would be used when both |
|
|
|
| are clipped (RM7888 only). |
|
|
|
|
|
|
| |
|
|