Heat Controller HMG**F1E General Information, Before You Install this Unit, Minimum Clearances

Page 4

GENERAL INFORMATION

This appliance has been tested for capacity and efficiency in accordance with AHRI Standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards. Please read all instructions before installing the unit.

Before You Install this Unit

This equipment is securely packaged at the time of shipment and upon arrival should be carefully inspected for damage prior to installing the equipment at the job site.Claims for damage (apparent or concealed) should be filed immediately with the carrier.

it is recommended that the cooling load of the area to be conditioned should be calculated and a system of the proper capacity selected.

Check the electrical supply and verify the power supply is adequate for unit operation.The system must be wired and provided with circuit protection in accordance with local building codes. If there is any question concerning the power supply, contact the local power company.

Verify the duct system is appropriate for the air handler being installed. Please note that when replacing an existing system with lower air-flow, the duct system may require modification.

Locating the Air Handler

Survey the job site to determine the best location for mounting the unit. Consideration should be given to availability of electric power, service access, and noise.

The dimensions of the room or alcove must be able to accommodate the overall size of the unit and the installation clearances listed in Table 1. Physical dimensions for this air handler are also shown in Figure 12 (page 17).

The air handler should be set into position before routing the refrigerant tubing.

Minimum Clearances

This appliance must be installed in accordance with clearances listed in Table 1. The air handler must be installed with ample clearance for easy access to the air filter, blower assembly, heater assembly, controls, and vent connections. Applicable building codes may require additional clearance to equipment. Refer to applicable building codes for details.

Static pressure drop through louvered openings and through return air plenums should be considered in the overall duct design in the determination of the total external static pressure.

Operation of Air Handler During Construction

CAUTION:

Failure to follow these instructions will void the factory warranty and may significantly reduce the life or the performance of the air handler, and/or result in other unsafe conditions. It is the responsibility of the installing contractor to insure these provisions are met.

Operating an air handler in a construction environment can cause the appliance a variety of problems. Proper use of commercial portable space heating equipment during construction is recommended. This air handler may be used during construction if it is not in violation of any applicable codes and the following criteria are met:

The installation must meet all applicable codes and be permanently installed according to the instructions supplied with the air handler including electrical supply and duct work.

The air handler must be controlled by a properly installed thermostat that complies with the current provisions of the NEC (ANSI/NFPA 70) and all applicable codes having jurisdiction. Thermostat connections must be made in accordance with instructions supplied with the air handler and thermostat. See pages 11 - 12.

The installation must include a properly installed filter in the return air system with no by-pass air.The filter must be inspected frequently and replaced when necessary.

Return air must be supplied unrestricted and located such that dust and gases from construction activity are not introduced into the circulating air system.

Before occupying the structure: The filter must be replaced or cleaned, the duct work must be inspected and cleaned of any construction debris, and the air

INSTALLATION CLEARANCES

Left Side

......... 0 Inches

Right Side

....... 0 Inches

Back

0 Inches

Front

See Notes

 

REAR

 

 

LEFT

RIGHT

 

 

SIDE

SIDE

 

FRONT

NOTES:

Alcove Installations - Allow 24 in. minimum clearance from front of unit to nearest wall or partition for servicing. Recommended clearance is 36 in.

Table 1. Minimum Unit Clearances

4

Image 4
Contents AIR Handler Table of Contents Important Safety Information NitrogenRequirements & Codes Health Flammability ReactivityBefore You Install this Unit General InformationLocating the Air Handler Minimum ClearancesInstallation in a Garage Plenums & Air DuctsUnconditioned Spaces Air FiltersAir handler Installation Downflow InstallationsPackaging Removal Mounting ApplicationsHorizontal Left Installations Horizontal InstallationsHorizontal Right Installations Refrigerant Line Connections NitrogenOrifice Removal & Installation Connecting the LinesetsCondensate Drainage Example Electrical connections Pre-Electrical ChecklistThermostat Connections Control Board TwinningStartup & Adjustments Electronic Air Cleaner EACHeater Kits HumidifierRefrigerant Charging Blower ConfigurationsAir Circulation Selecting Basic Heating Airflow Dehumidification OptionsSelecting Basic Cooling / Heat Pump Airflow Unit Maintenance TroubleshootingFigures & Tables Furnace Size Btuh Detail DBreaker 60A Heating Element Dry Coil ESP Airflow DataAirflow Data for HMG**F1E Series Air Handlers Airflow Data for HMG**X1E Air Handlers HCG24V1E & HCG30V1E CFMTON TON HCG36V1E & HCG42V1EAirflow Data for HCG**V1E Air Handlers HCG24V1E HCG30V1EHCG36V1E HCG42V1E HCG48V1E HCG60V1EElectrical diagrams & Data Single Stage Control BoardFixed Speed Motor Control Board Wiring Diagram for HMG**F1E Series Air HandlerAir Handler with Fixed Speed High Efficiency Motor Series Air HandlerWiring Diagram for HCG**V1E Series Air HandlerMCA MOP HMG**F1E SeriesH6HK Control Signal & Mode Operation Total KW Board Action Control Board OperationAir Handler Model Models NumberAUX Heat FAN Installer Name Installation Address