Heat Controller HMG**X1E, HMG**F1E Orifice Removal & Installation, Connecting the Linesets

Page 9

Orifice Removal & Installation

The orifice installed in the air handler has been sized for use with the most popularly matched outdoor units. The orifice size as shipped from the factory is listed on the air handler rating plate. Perform steps 1 - 9 to confirm that the orifice size meets the requirements outlined in the outdoor unit installation manual.

1.Remove the cap from the end of the liquid line.

2.Verify pressurization by depressing the Schrader valve on the end of the liquid line. Listen for any escaping gas.

If there is no pressure, test the coil for leakage.

If leakage is found, clearly mark the location of the leak and return the coil to the distributor for processing.

If no leaks are found, the coil may be installed.

3.Depress the valve to relieve all pressure from the coil.

4.Remove and discard the valve core.

CAUTION:

To prevent damage to the unit or internal components, it is recommended that two wrenches be used when loosening or tightening nuts. Do not over tighten!

5.Using two wrenches, loosen the nut and distributor body as shown in Figure 6. Turn the assembly nut counter- clock-wise until the orifice body halves are seperated.

6.Insert a light-gauge wire hook between the distributor body and the restrictor orifice while being careful not to scratch either part. Carefully remove the restrictor orifice from the distributor body. See Figure 7.

7.Check the actual size of the new orifice. NOTE: The size is stamped on its side. Do not use pin gauges to measure the orifice diameter.

8.Insert the new orifice into the distributor body, rounded end down. See Figure 8.

CAUTION:

To prevent damage to the unit or internal components, it is recommended that two wrenches be used when loosening or tightening nuts. Do not over tighten!

9.Realign the assembly nut on the distributor body and hand tighten both components. Mark a line on both bodies and then tighten an additional 1/4 turn using two wrenches.The movement of the two lines will show how much the nut is tightened. If a torque wrench is used, tighten to 10-12 ft. lbs. or 14-16 Nm.

Figure 7. Removal of Orifice

Figure 8. Restrictor Insertion into Distributor Body

Connecting the Linesets

IMPORTANT NOTES FOR HORIZONTAL OR DOWNFLOW INSTALLATIONS WITH TXV VALVE:

The sensing bulb must be located flush against the suction line for optimum heat transfer.

Avoid attaching the sensing bulb to the lowest part of the suction line where condensate may accumulate.

Do not locate the sensing bulb on vertical sections of the lineset.

For horizontal lines, the bulb should not be located at 12 or 6 o’clock position of the suction line. The best location is at 4 or 8 o’clock.

For additional information on proper sensing bulb locations, please refer to the valve manufacturer’s instructions.

IMPORTANT: The steps in the Orifice Removal & Installation section must be performed before the linesets are connected.

Figure 6. Loosening of Nut & Distributor Body

9

Image 9
Contents AIR Handler Table of Contents Nitrogen Important Safety InformationRequirements & Codes Health Flammability ReactivityGeneral Information Before You Install this UnitLocating the Air Handler Minimum ClearancesPlenums & Air Ducts Installation in a GarageUnconditioned Spaces Air Filters Downflow Installations Air handler Installation Packaging Removal Mounting ApplicationsHorizontal Installations Horizontal Left InstallationsHorizontal Right Installations Nitrogen Refrigerant Line ConnectionsConnecting the Linesets Orifice Removal & InstallationCondensate Drainage Example Pre-Electrical Checklist Electrical connectionsThermostat Connections Twinning Control BoardElectronic Air Cleaner EAC Startup & AdjustmentsHeater Kits HumidifierBlower Configurations Refrigerant ChargingAir Circulation Dehumidification Options Selecting Basic Heating AirflowSelecting Basic Cooling / Heat Pump Airflow Troubleshooting Unit MaintenanceFurnace Size Btuh Detail D Figures & TablesBreaker 60A Heating Element Airflow Data Dry Coil ESPAirflow Data for HMG**F1E Series Air Handlers Airflow Data for HMG**X1E Air Handlers CFM HCG24V1E & HCG30V1ETON TON HCG36V1E & HCG42V1EHCG24V1E HCG30V1E Airflow Data for HCG**V1E Air HandlersHCG36V1E HCG42V1E HCG48V1E HCG60V1ESingle Stage Control Board Electrical diagrams & DataFixed Speed Motor Control Board Handler Wiring Diagram for HMG**F1E Series AirSeries Air Handler Air Handler with Fixed Speed High Efficiency MotorHCG**V1E Series Air Handler Wiring Diagram forHMG**F1E Series MCA MOPH6HK Control Board Operation Control Signal & Mode Operation Total KW Board ActionAir Handler Model Models NumberAUX Heat FAN Installation Address Installer Name