Heat Controller HMG**X1E Air handler Installation, Packaging Removal, Mounting Applications

Page 6

equipment noise eminating from the air handler. These treatments can produce a quieter installation, particularly in the heated space. However, they can increase the pressure drop in the duct system. Care must be taken to maintain the proper maximum pressure rise across the air handler, temperature rise and flow rate. This may mean increasing the duct size and/or reducing the blower speed. These treatments must be constructed and installed in accordance with NFPA and SMACNA construction standards. Consult with local codes for special requirements. For best sound performance, be sure to install all the needed gaskets and grommets around penetrations into the air handler, such as for electrical wiring.

Air handler INSTALLATION

The HMG**F1E, HMG**X1E & HCG**V1E Series Air Handler is shipped ready for vertical upflow installation and is approved for attic, basement, alcove/closet or crawlspace installation with zero clearance to combustibles. See Table 1 (page 4) for required installation clearances. This appliance is approved only for indoor use.

The unit must be leveled at installation and attached to a properly installed duct system.

The surface that the air handler is mounted on must provide sound physical support of the unit.

The air handler must be installed so that all electrical components are protected from water.

If a louvered door is installed across the front of this unit, the appliance must be mounted flush or behind front edge of finished wall.

Always reinstall the doors on the air handler after servicing or cleaning/changing the filters.Do not operate the air handler without all doors and covers in place.

Packaging Removal

Remove the shipping crate and User’s Manual from the equipment. When removing the crate, use extra care so tubing connectios are not damaged. Do not pull on the coils upper tubes.

Mounting Applications

Vertical only air handlers are factory ready for upflow applications. These units may be applied in downflow applications when applied with the appropriate field kit.

Factory ready horizontal air handlers may be applied in upflow or horizontal-left and -right discharge applications. These units may also be applied in downflow discharge when applied with the appropriate field kit as specified in the units Technical Specifications.

Through-the-floor installations require a 1/4” thick noncombustible resilient gasket to be used whenever the supply or return air ducts pass through the floor.The gasket should be positioned between the duct, unit, and floor.

Horizontal

Drain Pan

Return

Air

Figure 1. Upflow Installation

Upflow Installations

All air handlers are factory shipped, ready for upflow installation. The horizontal drain pan may be removed from the air handler when installing the unit in an upflow configuration. All return air must enter from the bottom of the unit. A typical upflow unit is shown in Figure 1.

Downflow Installations

The downflow accessory kit (SeeTechnical Specifications) is required for downflow applications. Instructions for installing the downflow accessory kit are included with the kit.It is recommended that the accessory be installed prior to installing the unit. All return air in downflow applications must enter through the top of the unit. A typical installation of the unit in a downflow application is shown in Figure 2.

Cabinet

Tube

Close-off

Plate

Adaptor Kit

Coil

Figure 2. Downflow Installation

6

Image 6
Contents AIR Handler Table of Contents Requirements & Codes Important Safety Information Nitrogen Health Flammability ReactivityLocating the Air Handler Before You Install this UnitGeneral Information Minimum ClearancesUnconditioned Spaces Installation in a GaragePlenums & Air Ducts Air FiltersPackaging Removal Air handler InstallationDownflow Installations Mounting ApplicationsHorizontal Installations Horizontal Left InstallationsHorizontal Right Installations Refrigerant Line Connections NitrogenOrifice Removal & Installation Connecting the LinesetsCondensate Drainage Example Pre-Electrical Checklist Electrical connectionsThermostat Connections Control Board TwinningHeater Kits Startup & AdjustmentsElectronic Air Cleaner EAC HumidifierBlower Configurations Refrigerant ChargingAir Circulation Dehumidification Options Selecting Basic Heating AirflowSelecting Basic Cooling / Heat Pump Airflow Unit Maintenance TroubleshootingFigures & Tables Furnace Size Btuh Detail DBreaker 60A Heating Element Airflow Data Dry Coil ESPAirflow Data for HMG**F1E Series Air Handlers Airflow Data for HMG**X1E Air Handlers TON HCG24V1E & HCG30V1ECFM TON HCG36V1E & HCG42V1EHCG36V1E HCG42V1E Airflow Data for HCG**V1E Air HandlersHCG24V1E HCG30V1E HCG48V1E HCG60V1EElectrical diagrams & Data Single Stage Control BoardFixed Speed Motor Control Board Wiring Diagram for HMG**F1E Series Air HandlerAir Handler with Fixed Speed High Efficiency Motor Series Air HandlerWiring Diagram for HCG**V1E Series Air HandlerHMG**F1E Series MCA MOPH6HK Air Handler Model Control Signal & Mode Operation Total KW Board ActionControl Board Operation Models NumberAUX Heat FAN Installer Name Installation Address