Haier HPU-90CA03T3 operation manual Unit Clearances

Page 22
OUTDOOR UNIT

Installation procedure

Outdoor unit

2.UNIT CLEARANCES

10 "Min.

Service Access 18" Min.

Figure 1

10" Min.

Service Access

18" Min.

10"

10 "

The minimum clearances for the unit are illustrated in Figure 1. Condenser air enters from three sides. Air discharges upward from the top of the unit. Refrigerant tube and electrical connections are made from the service access area. The most common application will find the unit best located about 10" from back wall with connection side facing the wall. This application minimizes exposed tubing and wiring, minimizing the space for youngsters to run around the unit with subsequent damage to the tubing or wiring.

In more confined application spaces, such as corners provide a minimum of 10" clearance on all air inlet sides. For service access to the compressor and control box, allow 18" minimum clearance. Ensure top is unobstructed. If units are to be located under an overhang, there should be a minimum of 36" clearance and provision made to deflect the warm discharge air out from the overhang.

In order to have an unrestricted air flow, owners should be advised to avoid lawn mower discharge toward the unit depositing debris on the fin coil surface reducing the unit efficiency.

.3.REFRIGERANT PIPING

The refrigerant piping is very important as it affects the proper operation and efficiency of the air conditioning system. Note the following guidelines:

OUTDOOR UNIT

PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FOR EVERY 10' OF LINE

INDOOR UNIT ABOVE OR

LEVEL TO OUTDOOR UNIT

30m

MAX.

LIQUID LINE SUCTION LINE OIL TRAP WHEN INDOOR UNIT IS 4 FEET OR M O R E B E L O W

ADDITIONAL SUCTION LINE OIL TRAP FOR EACH 20 FOOT RISE OF PIPE

INDOOR UNIT

LIQUID LINE

A

INDOOR UNIT

OUTDOOR UNIT

INDOOR UNIT BELOW OUTDOOR UNIT

6'B-1

INVERTED LOOP

 

LIQUID LINE

INDOOR UNIT

 

OUTDOOR UNIT

30m

MAX.

 

SUCTION LINE

B-2

21

Image 22
Contents Cabinet unit Name of Parts Outdoor unitParts and Functions Operation points Safety Precautions Applicable ambient temperature rangeOperation Unit startFan Operation Users’ Attention Windows should be hung with curtains or blindsMaintenance Remove air inlet grilleAfter season maintenance Trouble shooting Followings are not problemsWhen problems occur? Switch is not set At onWhen Troubles Occur ? SymptomInstallation instruction Installation instruction Standard accessoriesInstallation procedure Before installationInstallation procedure Installation of indoor unitInstallation of fall-prevention fitting metal Indoor unit Slope Good Main points of installation refrigerant pipe Outdoor unit Unit Clearances Tubing connection Matters needing attention Check for leakage Vacuum PumpingOpen all valves Refrigerant chargeRefill refrigerant Heat isolation of the pipesPressing method of connection wire Wiring method Wiring method of orbicular terminalConnect wire between indoor & outdoor unit Others Calculation of refrigerant density Preventive measures against excess of critical valuePage