Installation procedure

Outdoor unit

Check for leakage

In the case of pressure decrease during steps 1 to 3 ,check the joints with the ear,hand or soapsuds for leakage.Repair it by welding or tighten the connecting nut up.

Vacuum Pumping

Use vacuum pump to evacuate the air.Never use the refrigerant for the evacuation.

Drain off the nitrogen gas after the leak test and then connect the vacuum pump as shown in the figure below.

The vacuum pumping must be done from both the liquid and gas inlets.

Low-pressure High-pressure

gauge gauge

 

 

 

Three-way valve fully

Indoor

Outdoor

 

closed(gas side)

VL VH

 

 

Gauge distributor

 

 

 

 

Solder joint

 

Solder joint

Access hole

 

 

 

 

6.4

 

 

 

 

Copper

pipe

Tightly

Solder

 

closed

 

joint

Access hole

 

 

 

Indoor unit

Outdoor unit

Three-way valve fully closed liquid side

Detailed diagram of the three-way valve

6.4Relief valve

Copper pipe

Nitrogen bottle

To the gauge

 

 

distributor

 

(Gas side)three-way valve

 

 

 

(Liquid side)three-way valve

 

 

To the unit

(Gas side )

 

access hole

 

 

(Liquid side)access hole

 

 

To the unit

Field tube

 

installation

Field tube

 

 

installation

Use a vacuum pump with high degree of vacuum(below-755mmHg) and large volume displacement (above 40L/min)

The pumping time depends on the length of the connecting pipe.Generally,it takes about 2-3 hours. Make sure that the Y-shaped valves on both the gas and liquid sides are closed before pumping.

If the vacuum can no reach-755mmHg within 2 hours,continue pumping for another 1 hour.

If the vacuum can no reach-755mmHg after more than 2 hour's pumping,close the valves VL and VH onthe gauge distributor and stop pumping.One hour later,check the vacuum again.If the vacuum has changed,it means there is a leakage.Repair it.

After the above steps,replace the vacuum pump with the refrigerant pump and refill refrigerant.

24

Image 25
Contents Cabinet unit Outdoor unit Name of PartsParts and Functions Operation points Applicable ambient temperature range Safety PrecautionsUnit start OperationFan Operation Windows should be hung with curtains or blinds Users’ AttentionRemove air inlet grille MaintenanceAfter season maintenance Followings are not problems Trouble shootingSwitch is not set At on When problems occur?Symptom When Troubles Occur ?Installation instruction Standard accessories Installation instructionBefore installation Installation procedureInstallation of indoor unit Installation procedureInstallation of fall-prevention fitting metal Indoor unit Slope Good Main points of installation refrigerant pipe Outdoor unit Unit Clearances Tubing connection Matters needing attention Vacuum Pumping Check for leakageRefill refrigerant Refrigerant chargeOpen all valves Heat isolation of the pipesPressing method of connection wire Wiring method Wiring method of orbicular terminalConnect wire between indoor & outdoor unit Others Preventive measures against excess of critical value Calculation of refrigerant densityPage