Haier HPU-90CA03T3 operation manual Calculation of refrigerant density

Page 29
An example
Refrigerant density:0.3(kg/m3)

Others

1.Calculation of refrigerant density

Calculation will be made according to the following methods:

1)Total refrigerant content of each system (kg) =content of 1 outdoor system + refilled refrigerant Content of 1 outdoor system:Factory filled refrigerant

Refilled refrigerant:Filled content during installation according to the diameter and length of the liquid piping.

2)Calculation of the minimum room space (m3).

3)Calculation of refrigerant density

Total refrigerant content

Minimum room space

2.Preventive measures against excess of critical value

1) Make ventilation holes

Ventilation holes should be built above and under the door.The area of each hole should not be smaller than 0.15% of the room space.Holes can be made directly in the wall.

2) Reduce the filling content of refrigerant

Filling content of refrigerant can be reduced by shortening the distance between the indoor and outdoor units.

By reducing the capacity of the outdoor unit.

When outdoor unit be made up of several units.the outdoor capacity of each system should reduce.So the refrigerant content of system reduce.

3) Install ventilation fans.

Users can install uninterrupted ventilation fans to keep the refrigerant density under the critical value. If uninterrupted ventilation is impossible,a combined fanning and alarming device should be installed in its stead (through which immediate ventilation is possible when leak occurs).

(See the figure below)

Ventilation fan and gas leak alariming device

The gas leak alarming

Vertilation opening

device should be installed

 

at refrigerant gas

 

stagnation areas

 

28

Image 29
Contents Cabinet unit Outdoor unit Name of PartsParts and Functions Operation points Applicable ambient temperature range Safety PrecautionsUnit start OperationFan Operation Windows should be hung with curtains or blinds Users’ AttentionRemove air inlet grille MaintenanceAfter season maintenance Followings are not problems Trouble shootingSwitch is not set At on When problems occur?Symptom When Troubles Occur ?Installation instruction Standard accessories Installation instructionBefore installation Installation procedureInstallation of indoor unit Installation procedureInstallation of fall-prevention fitting metal Indoor unit Slope Good Main points of installation refrigerant pipe Outdoor unit Unit Clearances Tubing connection Matters needing attention Vacuum Pumping Check for leakageRefill refrigerant Refrigerant chargeOpen all valves Heat isolation of the pipesConnect wire between indoor & outdoor unit Wiring method Wiring method of orbicular terminalPressing method of connection wire Others Preventive measures against excess of critical value Calculation of refrigerant densityPage