Installation procedure

Outdoor unit

Matters needing attention

Never use oxygen,flamable and poisonous gases for the leak test.

Low-pressure High-pressure

gauge gauge

 

 

 

Three-way valve fully

Indoor

Outdoor

 

closed(gas side)

VL VH

 

 

Gauge distributor

 

 

 

 

Solder joint

 

Solder joint

Access hole

 

 

 

 

6.4

 

 

 

 

Copper

pipe

Tightly

Solder

 

closed

 

joint

Access hole

 

 

 

6.4Relief valve

Copper pipe

bottle

Indoor unit

Outdoor unit

Nitrogen

Three-way valve fully closed liquid side

Detailed diagram of the three-way valve

To the gauge

 

 

distributor

 

(Gas side)three-way valve

 

 

 

(Liquid side)three-way valve

 

 

To the unit

(Gas side )

 

access hole

 

 

(Liquid side)access hole

 

 

To the unit

Field tube

 

installation

Field tube

 

 

installation

Step 1:Charge for more than 3 minutes under 0.3MPa(3.0kg/cm2g) Step 2:Charge for more than 3 minutes under 1.5MPa(15kg/cm2g)

--Serious leakage may be found.

Step 3:Charge for more than 24 hours under 3.0MPa(30kg/cm2g) --Small leakage may be found.

Check for pressure decrease Without pressure decrease-Pass

With pressure decrease-Check for leakge.

There will be a 0.01MPa(0.1kg/cm2g) pressure change for every 1 C ambient temperature change during the 24-hour pressure charge.It should be corrected during the test.

23

Image 24
Contents Cabinet unit Name of Parts Outdoor unitParts and Functions Operation points Safety Precautions Applicable ambient temperature rangeOperation Unit startFan Operation Users’ Attention Windows should be hung with curtains or blindsMaintenance Remove air inlet grilleAfter season maintenance Trouble shooting Followings are not problemsWhen problems occur? Switch is not set At onWhen Troubles Occur ? SymptomInstallation instruction Installation instruction Standard accessoriesInstallation procedure Before installationInstallation procedure Installation of indoor unitInstallation of fall-prevention fitting metal Indoor unit Slope Good Main points of installation refrigerant pipe Outdoor unit Unit Clearances Tubing connection Matters needing attention Check for leakage Vacuum PumpingRefrigerant charge Refill refrigerantOpen all valves Heat isolation of the pipesWiring method Wiring method of orbicular terminal Pressing method of connection wireConnect wire between indoor & outdoor unit Others Calculation of refrigerant density Preventive measures against excess of critical valuePage