Installation procedure

Outdoor unit

Adding refrigerant

Refrigrant must be added in liquid state. Refrigerant bottle swith or without a siphon tube can be refilled with refrigerant upright or upside down,Respectively.

Containers for R22 refrigerant must be marked with R22

R22 refrigerant cannot share the same instrument distributor and filling pipes.

Refrigerant charge

After finished vacuum the system,charge the vacuum to the refrigerant pump,chargeing the refrigerant.

Calculation of the refrigerant charge

Note:when unit shipping out of the factory,charge the refrigerant not including the connstruction procedure charged parts.

The calculation of the refrigerant charging:

When the connection pipe(L)<=5 meters, not need to add refrigerant;If the connection pipe (L)> 5 meters,we need recharge the 60g refrigerant per add 1 meter.

That is :the quantity of refrigerant charging=(L-5)*60(g)

Refill refrigerant

When the outdoor valve is shut,fill the refrigerant from the access hole at the gas and liquid sides.

If the required filling is impossible,open all the gas and liquid valves,then slightly shut the gas valve, run the compressor and fill the refrigerant from the access hole at the gas side.Now adjust the gas valve to control the refrigerant flow,which will be gasified during absorption by the system.

If there is insufficient refrigerant in the system caused by leaks,refill it after the remaining refrigerant is recollected.

Open all valves

Open all the valves of the outdoor unit.

Heat isolation of the pipes

Separate isolation should be made for the liquid and gas pipes.

Materials used for the pipe isolation at the gas side must withstand above 120 C temperature.

25

Image 26
Contents Cabinet unit Name of Parts Outdoor unitParts and Functions Operation points Safety Precautions Applicable ambient temperature rangeOperation Unit startFan Operation Users’ Attention Windows should be hung with curtains or blindsMaintenance Remove air inlet grilleAfter season maintenance Trouble shooting Followings are not problemsWhen problems occur? Switch is not set At onWhen Troubles Occur ? SymptomInstallation instruction Installation instruction Standard accessoriesInstallation procedure Before installationInstallation procedure Installation of indoor unitInstallation of fall-prevention fitting metal Indoor unit Slope Good Main points of installation refrigerant pipe Outdoor unit Unit Clearances Tubing connection Matters needing attention Check for leakage Vacuum PumpingOpen all valves Refrigerant chargeRefill refrigerant Heat isolation of the pipesConnect wire between indoor & outdoor unit Wiring method Wiring method of orbicular terminalPressing method of connection wire Others Calculation of refrigerant density Preventive measures against excess of critical valuePage