INSTALLATION | ||
|
|
|
Table A.1 lists recommended cable sizes and lengths for rated current and duty cycle. Length refers to the distance from the welder to the work and back to the welder. Cable diameters are increased for long cable lengths to reduce voltage drops.
TABLE
TOTAL COMBINED LENGTH OF ELECTRODE AND WORK CABLES
The auxiliary power capacity is 9,000 Watts Peak, 8500 Watts Continuous of 60 Hz, single phase power. The auxil- iary power capacity rating in watts is equivalent to volt- amperes at unity power factor. The max permissible current of the 240 VAC output is 35 Amps. The 240 VAC output can be split to provide two separate 120 VAC outputs with a max permissible current of 35 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paral- leled). Output voltage is within ± 10% at all loads up to rated capacity. All auxiliary power is protected by circuit
Cable Length
Cable Size for
250Amps
100% Duty Cycle
1 AWG
1AWG 1/0 AWG
breakers.
The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the cur- rent capacity of the associated receptacle.
NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paralleled.
CABLE INSTALLATION
Install the welding cables to your RANGER 250 as fol- lows.
1.The engine must be OFF to install welding cables.
2.Remove the flanged nuts from the output terminals.
3.Connect the electrode holder and work cables to the weld output terminals. The terminals are identi- fied on the case front.
4.Tighten the flanged nuts securely.
5.Be certain that the metal piece you are welding (the “work”) is properly connected to the work clamp and cable.
6.Check and tighten the connections periodically.
• Loose connections will cause the output termi-
CAUTION
nals to overheat. The terminals may eventually melt.
•Do not cross the welding cables at the output terminal connection. Keep the cables isolated and separate from one another.
AUXILIARY POWER RECEPTACLES
The auxiliary power of the RANGER 250 consists of two 20
STANDBY POWER CONNECTIONS
The RANGER 250 is suitable for temporary, standby or emergency power using the engine manufacturer’s recom- mended maintenance schedule.
The RANGER 250 can be permanently installed as a stand- by power unit for 240 VAC, 3 wire, single phase, 35 amp service. Connections must be made by a licensed electri- cian who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.
1.Install the
2.Take necessary steps to assure load is limited to the capacity of the RANGER 250 by installing a 40 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 35 amperes. Loading above the rated output will reduce output voltage below the allowable - 10% of rated voltage which may damage appliances or other
3.Install a 50 amp, 120/240 VAC plug (NEMA Type
4.Plug this cable into the 50 Amp, 120/240 Volt receptacle on the RANGER 250 case front.
RANGER 250