Lincoln Electric 225 manual Auxiliary Power While Welding, Simultaneous Welding and Power

Page 16

A-9

INSTALLATION

A-9

 

 

 

Auxiliary Power While Welding

It must be noted that the above auxiliary power ratings are with no welding load. Simultaneous welding and power loads are permitted by following Table III. The permissible currents shown assume that current is being drawn from either the 115V or 230V supply (not both at the same time). Also, the “Output Control” is set at “10” for maximum auxiliary power.

TABLE III

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

Setting

Watts (Unity Power

Current in Amperes

 

Factor)

@ 115V

-or- @ 230V

 

 

 

 

Max. Stick or Wire

 

 

 

Feed Setting

None

0

0

 

 

 

 

175 Stick Setting

2100

18

9

 

 

 

 

125 Stick Setting

3800

32

16

 

 

 

 

90 Stick Setting

5000

42

21

 

 

 

 

70 Stick Setting

5600

48

24

 

 

 

 

50 Stick Setting

6300

54

27

 

 

 

 

NO WELDING

8000

70

35

 

 

 

 

Standby Power Connections

The Weldmark 225 is suitable for temporary, standby, or emergency power using the engine manufacturer’s recommended maintenance schedule.

The Weldmark 225 can be permanently installed as a standby power unit for 230V-3 wire, single phase 35 ampere service.

WARNING

(Connections must be made by a licensed electri- cian who can determine how the 115/230V power can be adapted to the particular installation and comply with all applicable electrical codes.) The following information can be used as a guide by the electrician for most applications (refer also to the connection diagram shown in Figure 1.)

1.Install a double pole, double throw switch between the power company meter and the premises disconnect.

Switch rating must be the same or greater than the customer’s premises disconnect and service overcurrent protection.

2.Take necessary steps to assure load is limited to the capacity of the Weldmark 225 by installing a

35amp 230V double pole circuit breaker. Maximum rated load for the 230V auxiliary is 35 amperes. Loading above 35 amperes will reduce output voltage below the allowable -10% of rated voltage which may damage appliances or other motor-driven equipment.

3.Install a 50 amp 115/230V plug (NEMA type 14-50) to the Double Pole Circuit Breaker using No. 8,

4 conductor cable of the desired length. (The

50 amp 115/230V plug is available in the optional plug kit.)

4.Plug this cable into the 50 amp 115/230V receptacle on the Weldmark 225 case front.

WELDMARK 225

Image 16
Contents Weldmark Safety California Proposition 65 WarningsElectric Shock can kill Welding Sparks can cause fire or explosion IiiPrécautions DE Sûreté Sûreté Pour Soudage a L’ArcThank You Please Examine Carton and Equipment For Damage ImmediatelyTable of Contents Technical Specifications Weldmark 225 WEM InstallationHeight Width Depth Weight Specifications Installation Instructions Safety PrecautionsSpark Arrester Machine GroundingWelding Output Cables Pre-Operation ServiceAWG Connection of Wire Feeders Angle of OperationHigh Altitude Operation Location / VentilationAdditional Safety Precautions Auxiliary PowerInstructions Connection of K930- TIG Module to the WeldmarkDuplex Receptacles Motor StartingElectrical Device USE with the Weldmark Type Common Electrical Devices Possible ConcernsSimultaneous Welding and Power Auxiliary Power While WeldingStandby Power Connections Connection of Weldmark 225 to Premises Wiring Design Features Other FeaturesEngine Features OperationEngine ON-OFF Switch Engine Start Push-Button SwitchWeldmark 225 Approximate Fuel Consumption Welder Controls Function and OperationStarting/Shutdown Instructions Break-in PeriodWire Feed Welding Processes Constant Voltage Welding ProcessStick Constant Current Welding TIG Constant Current WeldingSummary of Welding Processes Stick AutoAccessories K1745-1 Single GAS Cylinder HolderWire Feed Recommended EquipmentStick TIGMaintenance Safety PrecautionsRoutine Maintenance Oil 100 HRS Oil Filter 200 HRSOverspeed is Hazardous Fram CA79Fram G1 Champion RC12YCTroubleshooting HOW to USE Troubleshooting GuideTroubleshooting Troubleshooting Diagrams WEM2239-1 Weldmark Kohler Wiring Diagram CodeConnection of Weldmark 225 to LN-7 & K240 Contactor KIT M17215-2 30-98E How To Read Shop Drawings New Lessons in Arc WeldingNeed Welding Training? Basic CoursePrecaucion Warnung Manufactured by Livcoln Electric Company