Setting Battery Types on the Main Unit
You can attach different types of
WARNING: Fire hazard
Incorrectly setting the battery type can lead to battery damage and a risk of fire.
The settings can be changed by adjusting the dip switches found on the main unit behind the display panel.
Battery | Dip Switch Setting | Bulk/Absorption | Float |
Type | Switch 1Switch 2 |
|
|
|
|
|
|
Fixed | OFFOFF | 13.5 | 13.5 |
Flooded | OFFON (default) | 14.4 | 13.5 |
GEL | ONOFF | 14.2 | 13.8 |
AGM | ONON | 14.3 | 13.4 |
|
|
|
|
To adjust the battery type setting:
By default the battery type is set to Flooded (OFFON).
1.Detach the Display Panel to expose the Dip Switches.
2.Use the tip of your fingernail or a small screw driver with a flat tip to adjust the switches.
OFFON
Switch 1 Switch 2