Studer Innotec C2324 COMPACT, C3548 Connect the Solarmodules Solar +/- Only for solar option

Page 11

STUDER INNOTEC

COMPACT

3.5.5Connect the Solarmodules: SOLAR +/- (Only for solar option)

Solar modules are connected on these terminals. Under no circumstances should any other energy source i.e. wind generator be connected to these terminals! Only solar modules must be connected with two cables +/-. Depending on the power of the modules, the cable cross section should be

2.5up to 6mm2 . Before connecting it is necessary to check with a Voltmeter that the voltage of the Module meets the following values:

C1312 17-25V/30A, C2324 34 – 45V/30A, C3548 68 – 90V/20A.

3.5.6Connection to Auxiliary Contact:

On these tree terminals is a potential free change-over contact). The maximal permitted current and voltage for this is 16A/250Vac. The DEL 5 “Contact active” show the position of them: alight mind active and off mind non-active. The schematic view of the connections on the front, show the relay in the non-active mode.

3.5.7Connection to Remote control:

The Remote Control RCC 01 is connected in the terminal marked „Remote control“ with a RJ11/8 connector. The Remote Control can be plugged IN or plugged OUT during any operation situation. Push in the connector, without forcing it, until you hear the „click“, now the connector is locked in place. The same applies to the plug in the Remote Control. The length of the cable for Remote Control should not exceed 40m. We deliver it with 20m cable.

3.5.8Connection to Temperature Sensor (Temp.):

The Temperature sensor CT-35 is connected in the terminal marked „Temp“ with a RJ11/6 connector. The Temperature Sensor can be plugged IN or plugged OUT during any operating situation. Push in the connector without forcing it, until you hear a „click“, now the connector is locked in place. The Temperature Sensor must be glued to the wall of the battery or near it. The Temperature Sensor cable must not be tied together with the battery cables or laid in a rope/bundle.

User manual

COMPACT V2.0 E

11

Image 11
Contents Compact V2.0 E User and installer ManualIndex table Reset Value Battery Voltages and Absorption Time General Information Special Precautions Description of main functions Principe schematicIntroduction Parallel Connection Battery connectionsRemote control Solar charge regulator optionalConnection AssemblyPlace of assembly FixingSolar + Connecting Plan / Front sideProtection cover for the terminals connections Cabling/wiring Connection to Auxiliary Contact Connection to Remote controlConnection to Temperature Sensor Temp Connect the Solarmodules Solar +/- Only for solar optionDisplay and operating control elements OperatingTurning Knobs Light Emitting DiodesPush buttons Overload Battery ConditionInverter Charge detection system „StandbyEqualization charging Battery chargerInput current repartition Power sharing Cycle of chargeCharging current Transfer systemMultifunctional Contact Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Solar charge regulator optionMaximum Contact load -230Vac /16Amp-30Vdc/1A Remote ControlBattery voltages and absorption time Temperature sensorStandard setting Reset valueLED11 Program the auxiliary contactSet the voltage and timing threshold These four red LED show the function SetManual operating of Auxiliary Contact ExampleDiagram of the different mode MaintenanceVarious data Technical DataType Solar Charge Regulator-Floating