APC VS 50, VS 100 user manual Alarm, Description, Default Settings, Menu Location, Page

Models: VS 50 VS 100

1 65
Download 65 pages 5.73 Kb
Page 57
Image 57

ALARM/

DESCRIPTION

DEFAULT SETTINGS

[MENU LOCATION]

 

 

System LT Alm

The System Temperature is below the

Minor

[System/DC Parameters]

System Low Temperature threshold. Not

 

 

the same as battery temperature alarm.

 

Low Voltage Alarm

The System Voltage is below the System

Minor

[Power Modules/Rectifiers]

Low Voltage threshold. Not the same as

 

 

battery voltage alarm.

 

LVD Alarm

The controller opened the LVD. If unit

Major

[Batteries/LVD]

has a battery LVD, no power will be

 

 

available to turn on any Output Relays.

 

User Output Relay 1 Alarm

Output Relay 1 Alarm can be “mapped”

Ignore

[I/O/Output]

to activate other output relays (“Ignore”

 

 

activates no additional relays).

 

Rectifier 1-of-N Alm

Rectifier Fail 1-of-N alarm occurs. This is

Minor

[Power Modules/Rectifiers]

a special rectifier alarm group that

 

 

signifies that one rectifier has at least

 

 

one alarm condition.

 

Rectifier 2-of-N Alm

Rectifier Fail 2-of-N alarm occurs This is

Major

[Power Modules/Rectifiers]

a special rectifier alarm group that

 

 

signifies that more than one rectifier has

 

 

at least one alarm condition.

 

Rectifier Current Limit Alarm

A rectifier is in the current limited mode.

n of N

[Power Modules/Rectifiers]

 

 

Rectifier Fan Fail Alm

A rectifier fan has failed.

n of N

[Power Modules/Rectifiers]

 

 

Rectifier RFA Alarm

A rectifier output has failed.

n of N

[Power Modules/Rectifiers]

 

 

Magnum VS –48 Vdc User’s Manual

Page 52