APC VS 50, VS 100 user manual AC Power Cord Sets, 3-3 AC Input Wiring, 3-5 Power Cord Sets

Models: VS 50 VS 100

1 65
Download 65 pages 5.73 Kb
Page 11
Image 11
Figure 3.3-3 AC Input Wiring

Rectifier

Terminal #

Function

Terminal #

Function

Terminal #

Function

Rectifier 1

TRM2

Ground

TRM5

Line or Neutral

TRM8

Line

Rectifier 2 & 3

TRM3

Ground

TRM6

Line or Neutral

TRM9

Line

Rectifier 4 & 5

TRM4

Ground

TRM7

Line or Neutral

TRM10

Line

Chassis

TRM1

Ground

 

 

 

 

Figure 3.3-3 AC Input Wiring

AC Power Cord Sets

AC input cable kits are available from APC. These cables are 12 feet (3.7m) long and have a power plug installed on each cable. When ordered with the power system, these cables will be installed with strain reliefs provided to mount the 3-conductor jacketed cables. Each kit will supply power to the entire power system. Use the chart in Figure 3.3-5 to determine the suggested cable kits.

Part Num.

AWG

Cable Qty

Plug Num.

Plug Style

Voltage

Power System

0M-91157

14

3

NEMA 5-15

Non-locking

115

Magnum VS 50

0M-91155

14

3

NEMA L5-15

Locking

115

Magnum VS 50

0M-91156

12

2

NEMA 5-20P

Non-locking

115

Magnum VS 50

0M-91154

12

2

NEMA L5-20P

Locking

115

Magnum VS 50

0M-91158

10

1

NEMA 5-50P

Non-locking

115

Magnum VS 50

0M-1150

12

2

NEMA L6-20P

Locking

230

Magnum VS 50

0M-91160

10

1

NEMA 6-30P

Non-locking

230

Magnum VS 50

0M-91159

10

1

NEMA L6-30P

Locking

230

Magnum VS 50

0M-91137

12

6

NEMA 5-15P

Non-Locking

115

Magnum VS 100

0M-91140

12

6

NEMA L5-15P

Locking

115

Magnum VS 100

0M-91138

12

4

NEMA 5-20P

Non-locking

115

Magnum VS 100

0M-91141

12

4

NEMA L5-20P

Locking

115

Magnum VS 100

0M-91139

10

2

NEMA 5-50P

Non-locking

115

Magnum VS 100

0M-1149

12

4

NEMA L6-20P

Locking

230

Magnum VS 100

0M-91135

10

2

NEMA 6-30P

Non-locking

230

Magnum VS 100

0M-91136

10

2

NEMA L6-30P

Locking

230

Magnum VS 100

Figure 3.3-5 Power Cord Sets

WARNING: Hazardous ac voltage levels are present inside the power system. Keep the rear cover in place when the system is operational or energized.

The rear cover of each shelf in the power system is provided with two 1.125-inch (2.858 cm) diameter holes for electrical conduit. Conduit can be run to each shelf or strain reliefs are provided to install jacketed cables.

Magnum VS –48 Vdc User’s Manual

Page 6

Page 11
Image 11
APC VS 50, VS 100 user manual AC Power Cord Sets, 3-3 AC Input Wiring, 3-5 Power Cord Sets