PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Output Relay 1 Alias

An alternate name (alias) can be

Output Relay 1

[System/Out-Rly/Alias]

assigned to Output Relay 1 if desired.

 

 

Output Relay 6 Alias

An alternate name (alias) can be

Output Relay 6

[System/Out-Rly/Alias]

assigned to Output Relay 6 if desired.

 

Output Relay 1 Delay

Delay between sensing of the alarm

0.00 seconds – 600.00

[I/O/Output]

condition and activation of the mapped

seconds, 0.00 seconds

relay. An alarm condition must exist for

 

longer than the delay to be activated.

 

 

 

Output Relay 6 Delay

 

 

[I/O/Output]

 

 

Rectifier 1-of-N Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

if Rectifier Fail 1-of-N alarm occurs. This

Output Relay 1-6

 

is a special rectifier alarm group that

 

 

signifies that one rectifier has at least

 

 

one alarm condition.

 

Rectifier 2-of-N Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

if Rectifier Fail 2-of-N alarm occurs This

Output Relay 1-6

 

is a special rectifier alarm group that

 

 

signifies that more than one rectifier has

 

 

at least one alarm condition.

 

Rectifier Configuration Alarm

Defines the output relay that is that is

Ignore, Minor, Major

[Power Modules/Rectifiers]

energized a rectifier is added to any

Output Relay 1-6, n of N

 

empty slot after the dc system is

 

 

powered up or configured. This feature

 

 

is supported by the standard SNMP card

 

 

monitor, but is not supported by this dc

 

 

system.

 

Rectifier Current Limit Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

or special rectifier alarm group n of N that

Output Relay 1-6, n of N

 

occurs when a rectifier has been forced

 

 

into the current limited mode.

 

Rectifier Current Output Status

A display of the dc output current for the

Status Only

{Status Only}

individual rectifier.

 

[Power Modules/Rectifiers]

 

 

Rectifier Description

Displays the model number of the

Status Only

{Status Only}

installed rectifier.

 

[Power Modules/Rectifiers]

 

 

Rectifier Diagnostic Alarm

This feature is not needed in this

Ignore, Minor, Major

[Power Modules/Rectifiers]

particular configuration.

Output Relay 1-6, n of N

Rectifier Fan Fail Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

or special rectifier alarm group n of N that

Output Relay 1-6,n of N

 

occurs when a rectifier fan has failed.

 

Rectifier Fan Fail Alarm Status

The status will be “ON” if the rectifier fan

Status Only

{Status Only}

has failed.

 

[Power Modules/Rectifiers]

 

 

Magnum VS –48 Vdc User’s Manual

Page 43

Page 48
Image 48
APC VS 100, VS 50 user manual Output Relay