Figure 6.4-1 Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

Settings in BOLD)

 

 

Alarms Item 1

Display of up to 16 active alarms. Scroll

Alarm Status Only

{Status Only}

up or down to select individual alarms.

 

[ALARMS]

 

 

[告警]

 

 

 

 

 

Battery Capacity

The total battery capacity in ampere-

0Ah – 10,000 Ah, 0 Ah

[SETUP/BATTERY/

hours of the entire battery array.

 

CAP]

Normally specified at 20 hour discharge

 

[设置 / 电池 / 容量]

rate.

 

 

 

 

 

 

Battery Current

Battery current measured by the system

Battery Current Status

{Status Only}

controller at the battery current shunt.

Only

[STATUS/BATTERY/

 

 

PARAMETERS]

 

 

[状态 / 电池 / 参数]

 

 

 

 

 

Battery Float Voltage

One of three parameters that control the

-56.5V - -47.0V,-54.00 V,

[SETUP/BATTERY/

dc output voltage. Set the Float Voltage

 

VOLTAGE/FLOAT]

to the desired 25°C battery temperature

 

[设置 / 电池 / 电压 /

per the battery manufacturers

 

recommendations.

 

浮充]

 

 

 

 

 

Battery Functional Test

Lowers the system voltage so a

ON, OFF

[SETUP/BATTERY/TEST]

discharge test of the battery is

 

[设置 / 电池 / 测试]

performed. ON – initiates a battery test.

 

Off – stops a test in progress.

 

Battery Functional Test Result

Displays the results of the last battery

FAIL, PASS,

[STATUS/BATTERY/TEST]

test.

INTERRUPTED, IN

[状态 / 电池 / 测试]

 

PROCESS, NOT

 

PERFORMED

Battery Maximum Recharge

One of three parameters that control the

0 – 500 A, 5 A

Current

dc output voltage. If Battery Current

 

[SETUP/BATTERY/CURRENT]

surpasses the Maximum Battery

 

[设置 / 电池 / 电流]

Recharge Current, the dc output voltage

 

will be reduced (the system limits the

 

 

charging current to this programmable

 

 

value).

 

Battery Mode Status

This will display the condition of the

Float, Equalizing or

[STATUS/BATTERY/MODE]

battery. Float is normal operation.

Discharge.

[状态 / 电池 / 模式]

Discharge means the rectifiers are not

 

producing enough current and the

 

 

batteries are discharging. Equalizing

 

 

means the voltage is above float voltage

 

 

to give the batteries an equalize charge.

 

Magnum VS –48 Vdc User’s Manual

Page 30

Page 35
Image 35
APC VS 50, VS 100 user manual 设置 / 电池 / 容量