Image 60

Magnum VS 50 Power System

Output Voltage (factory

54.0

Vdc

programmed)

 

 

 

 

 

 

Operating Voltage Range

47

– 56.5 Vdc

 

 

 

 

Rated Output Current

50

A

 

 

 

Efficiency

85% Typical

 

 

 

Over Voltage Protection

59.5

Vdc

 

 

 

Output Current

45

A Minimum Continuous at 115 Vac Input

 

52.5

A Minimum Continuous at 230 Vac Input.

 

 

 

Current Limit

46.5

A Maximum at 115 Vac Input

 

55.0

A Maximum at 230 Vac Input.

 

 

Power Output @ 54.5 Vdc

2450 W Continuous at 115 Vac Input

 

2850 W Continuous at 230 Vac Input

 

 

 

Magnum VS 100 Power System

 

 

 

 

Output Voltage (factory

54.0

Vdc

programmed)

 

 

 

 

 

 

Operating Voltage Range

47

– 56.5 Vdc

 

 

Rated Output Current

100 A

 

 

Efficiency

91% Typical

 

 

 

Over Voltage Protection

59.5

Vdc

 

 

 

Output Current

90

A Minimum Continuous at 115 Vac Input

 

105 A Minimum Continuous at 230 Vac Input.

 

 

 

Current Limit

93

A Maximum at 115 Vac Input

 

110 A Maximum at 230 Vac Input.

 

 

Power Output per Rectifier

4900 W Continuous at 115 Vac Input

@ 54.5Vdc

5700 W Continuous at 230 Vac Input

 

 

 

 

Magnum VS –48 Vdc User’s Manual