PARAMETER NAME/ | DESCRIPTION | SETTINGS (Default |
[MENU LOCATION] |
| settings in BOLD) |
|
| |
Hardware System Voltage | Defines the output relay that is energized | Ignore, Minor, Major |
Alarm | if there is a hardware failure in the | Output Relay |
[Power Modules/Rectifiers] | system voltage monitoring function. |
|
Hardware Temperature Alarm | Defines the output relay that is energized | Ignore, Minor, Major |
[System/DC Parameters] | if there is a hardware failure in the | Output Relay |
| system temperature monitoring function. |
|
High Temperature Alarm | Defines the output relay that is energized | Ignore, Minor, Major |
[System/DC Parameters] | if the System Temperature exceeds the | Output Relay |
| system high temperature threshold. Not |
|
| the same as battery temperature alarm. |
|
High Temperature Threshold | Ambient temperature measured inside | 0 °C – 100 °C, 70.0 °C |
[System/DC Parameters] | the controller. An alarm will be reported |
|
| if temperature is higher than the |
|
| temperature entered. Not the same as |
|
| battery temperature threshold. |
|
High Voltage alarm | Defines the output relay that is energized | Ignore, Minor, Major |
[Power Modules/Rectifiers] | if the System Voltage is above the | Output Relay |
| System High Voltage threshold. Not the |
|
| same as battery voltage alarm. |
|
High Voltage Threshold | DC voltage measured by the controller. | |
[Power Modules/Rectifiers] | An alarm will be reported if voltage is |
|
| higher than the voltage entered. Not the |
|
| same as battery voltage threshold. |
|
Imbalance Alarm | An alarm will be generated if the rectifiers | Ignore, Minor, Major |
[Power Modules/Rectifiers] | do not current share. This feature is | Output Relay |
| supported by the standard SNMP card |
|
| monitor, but is not supported by this dc |
|
| system. |
|
Input Relay 1 | Defines the output relay that is energized | Ignore, Minor, Major |
[I/O/Input] | when an external contact closure or | Output Relay |
| opening at the Input Relay 1 connection |
|
| changes state. | • |
• | • | • |
• | • | • |
• | • | Ignore, Minor, Major |
Input Relay 4 | Defines the output relay that is energized | Output Relay |
[I/O/Input] | when an external contact closure or |
|
| opening at the Input Relay 4 connection |
|
| changes state. |
|
Input Relay | This feature is supported by the standard | Input |
[I/O/Input] | SNMP card monitor, but is not supported |
|
| by this dc system. |
|
Input Relay | This feature is supported by the standard | 0.00 Seconds |
[I/O/Input] | SNMP card monitor, but is not supported |
|
| by this dc system. |
|
Low Temperature Alarm | Defines the output relay that is energized | Ignore, Minor, Major |
[System/DC Parameters] | if the System Temperature is below the | Output Relay |
| System Low Temperature threshold. Not |
|
| the same as battery temperature alarm. |
|
Magnum VS | Page 41 |