APC VS 100, VS 50 user manual Alarm Summary, Description, Default Settings, Menu Location, Page

Models: VS 50 VS 100

1 65
Download 65 pages 5.73 Kb
Page 56
Image 56

 

 

8

Alarm Summary

 

 

 

 

 

ALARM/

DESCRIPTION

DEFAULT SETTINGS

 

 

[MENU LOCATION]

 

 

 

Battery Discharge Alarm

The battery discharge current exceeds

Minor

 

[Batteries/Parameters]

the programmed battery discharge

 

 

 

 

threshold.

 

 

Battery High Temp Alm

The battery temperature exceeds the

Minor

 

[Batteries/Parameters]

Battery High Temperature threshold.

 

 

Battery Low Temp Alm

The Battery Temperature is below the

Minor

 

[Batteries/Parameters]

battery Low Temperature threshold.

 

 

Battery LV Alm

The dc output voltage is below the

Major

 

[Batteries/Parameters]

battery low voltage threshold.

 

 

Circuit Breaker Alm 1

The top Circuit Breaker in the top shelf is

Major

 

[Distribution/Breakers]

tripped.

 

 

Circuit Breaker Alm 2

The bottom Circuit Breaker in the top

Major

 

[Distribution/Breakers]

shelf is tripped

 

 

Circuit Breaker Alm 3

The top Circuit Breaker in the bottom

Major

 

[Distribution/Breakers]

shelf is tripped.

 

 

Circuit Breaker Alm 4

The bottom Circuit Breaker in the bottom

Major

 

[Distribution/Breakers]

shelf is tripped

 

 

FUSE Alm 1

Any of Fuse 1 through 4 is blown.

Major

 

[Distribution/Fuses]

 

 

 

FUSE Alm 2

Any of Fuse 5 through 8 is blown.

Major

 

[Distribution/Fuses]

 

 

 

FUSE Alm 3

Any of Fuse 9 through 12 is blown.

Major

 

[Distribution/Fuses]

 

 

 

FUSE Alm 4

Any of Fuse 13 through 16 is blown.

Major

 

[Distribution/Fuses]

 

 

 

Hardware Batt Temp Alm

There is a hardware failure in the battery

Minor

 

[Batteries Parameters]

temperature monitoring function.

 

 

Hardware Sys Volt Alm

There is a hardware failure in the system

Minor

 

[Power Modules/Rectifiers]

voltage monitoring function.

 

 

Hardware Sys Temp Alm

There is a hardware failure in the system

Minor.

 

[System/DC Parameters]

temperature monitoring function.

 

 

System HT Alm

The System Temperature exceeds the

Minor

 

[System/DC Parameters]

system high temperature threshold. Not

 

 

 

 

the same as battery temperature alarm.

 

 

System HV Alm

The System Voltage is above the System

Minor

 

[Power Modules/Rectifiers]

High Voltage threshold. Not the same as

 

 

 

 

battery high voltage alarm.

 

 

Input Relay 1

An external contact closure at the Input

Ignore

 

[I/O/Input]

Relay 1 connection.

 

 

 

 

 

 

 

 

 

 

An external contact opening at the Input

 

Relay 4 connection.

Ignore

 

Input Relay 4

 

 

 

[I/O/Input]

 

 

 

Magnum VS –48 Vdc User’s Manual

Page 51

Page 56
Image 56
APC VS 100, VS 50 user manual Alarm Summary, Description, Default Settings, Menu Location, Page